C-Series AS-i Master Module
Operating the AS-i
3.
Select Slave0 within the "Old Address" control.
4.
Select the new address (e.g. Slave2) within the "New Address" control.
5.
Click the button "Change Slave Address".
6.
If the indicator "Result Code" is 0, address assignment was successful.
7.4
Abbreviations used within the Status List Control
7.5
Protected Operating Mode
Only those slaves shall be activated which are both members of the list of detect-
ed slaves (LDS) and members of the list of projected slaves (LPS), and whose
configuration data image (CDI) value equals the permanent configuration data
(PCD) value for that specific slave.
1.
Follow steps 1-5 of section <Configuration Mode> to bring the AS-i network
to Configuration mode
2.
Click the "Operation Mode" control to change to "Protected Mode"
X (O.K.)
The configuration data for the detected AS-i slave matches
the stored configuration data.
D (Detected Only)
An AS-i slave is detected at this address, but it was not
stored before.
P (Projected Only)
An AS-i slave was stored at this address, but it was not
detected.
C (Type Conflict)
The configuration data for the detected AS-i slave does not
match the stored configuration data. The actual exiting con-
figuration of the connected AS-i slave is displayed.
F (Periph. Fault)
The AS-i slave has a peripheral error.
A (Duplicate Addr.)
Two AS-i slaves use the same address.