Appendix: The First Commissioning of AS-i
In this chapter an example is given of how to put an AS-i network into
operation quickly and easily and without the need for external devices.
The addressing of the components connected to the AS-i network can
be performed directly on the AS-i master. It is of course more comfort-
able to do the addressing with a hand-held programming device or with
the Windows software AS-i Control Tools. However, it is possible to con-
figure even complex networks using only the AS-i master.
What to do ?
How to go about it?
See to it that the AS-i master is properly
supplied with power.
Using AS-i master with power supply
“A”: Connect the AS-i power supply unit
to the terminals AS-i + and AS-i - of the
master, connect the ground terminal.
Using AS-i master with power supply
“N”: Connect the 24 V DC standard
power supply with the terminals 24 V
and 0 V of the master, connect the
ground terminal.
Turn on the power supply.
After the self-test: the LEDs “power”, “config err”, “U ASI” and “prj mode” are on.
The LCD shows “40”: the AS-i master is in the off-line phase. Shortly after that a
“41” will be displayed: the AS-i master stays in the detection phase.
Switch the device to the projecting
mode, if the yellow LED does not light
up.
Press the “mode”-button for approx. five
seconds.
The yellow LED “prj mode” lights up. The device is now in projecting mode.
Add a slave with the address 0 to the
AS-i line.
Connect the slave's terminals with the
terminals AS-i +/- of the master.
The green LED “ASI active” lights up. The LCD shows “0”. This means the AS-i
master has detected the slave.
Change the slave address to address 1.
Select address 1 by pressing the “set”
button shortly, if necessary repeatedly.
When a “1” appears on the display press
the “set” button for approx. five seconds
until the display blinks. Press again
shortly the “set” button to assign the new
address to the slave.
The AS-i master detects the slave with address 1 and displays “1”.
Connect another slave with address 0 to
the AS-i line and allocate the address 2
to it.
Connect the slave to the AS-i line. The
addressing is the same as for the previ-
ous slave.
The addresses of all slaves detected are now displayed sequentially.