AS-i/Modbus Gateway
Operation via Modbus
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Tel. +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
s
u
e
d
a
te
1
1
.1
.2
0
0
0
43
7.3.12 Function 65: user defined function #1
This function is used to read the name and version of AS-i/Modbus gateway:
P:
Defines the part of version-information.
B:
Number of data-bytes D1 to DB
D
1
... D
B
:
Version-information as null-terminated string.
P = 1:
Name of the master (32 characters, B = 33).
P = 2:
Version of the master (16 characters, B = 17).
P = 3:
Installed software (32 characters, B = 33).
else:
Version number (8 characters, B = 9).
“
Installed software
” is a string holding the capability of Host-Interface and AS-i master
as upper- and lower-chase characters.
The single characters have the following significance:
The position of the characters within the string is defined as follows:
„CBFE....DOA...WT“
7.3.13 Function 66: user defined function #2
This function is used to write the Control programs for AS-i Control (download).
S:
First address of program-bytes to write.
D:
16 program-bytes.
query message:
A
65
1
P
C
q,lo
C
q,hi
response message:
A
65
B
D
1
D
B
C
r,lo
C
r,hi
D/d
“
data_exchange_active
” is set (D) or cleared (d).
O/o
“
offline
” is set (O) or cleared (o).
A/a
“
auto_address_enable
” is set (A) or cleared (a).
W/w The Modbus-watchdog is active (W) or inactive (w).
T/t
The AS-i master front panel buttons are enabled (T) or disabled (t).
C/c
The answering master is an AS-i Control. An uppercase (C) indicates an
active control-program, while a lowercase (c) a cleared start-flag or an unfit-
ting AS-i Master state for control-program execution.
B/b
The AS-i master is bus-capable (B).
The Modbus-master ever signs (B).
F/f
The answering master is supplied witch the optional AS-i error counter.
E/e
The answering master is capable of the optional EMC-testmode.
query message:
A
66
18
S
hi
S
lo
D
1
D
16
C
q,lo
C
q,hi
response message:
A
66
2
S
hi
S
lo
C
r,lo
C
r,hi
Summary of Contents for AS-i/Modbus Gateway