AS-i/Modbus Gateway
Address-Table of the Modbus Interfaces
Subject to reasonable modifications due to technical advances
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Tel. +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
s
u
e
d
a
te
1
1
.1
.2
0
0
0
55
The AS-i/Modbus gateway can transmit up to 15 registers in one telegram.
Addresses with index correspond with the bits or bytes within one register: “Address
Bit” corresponds to the value 2 bit and “Address Byte” corresponds to the lower-/upper
half of the accessed register.
The bits 0, 4, 8 and 12 are connected with the data connection D0 of the AS-i slaves,
bits 1, 5, 9 and 13 with D1,
bits 2, 6, 10 and 14 with D2,
bits 3, 7, 11 and 15 with D3.
Data Input Image IDI
Address
Bit
Data element
0
0-3
4-7
8-11
12-15
data from slave 3
data from slave 2
data from slave 1
data from slave 0
1
0-3
4-7
8-11
12-15
data from slave 7
data from slave 6
data from slave 5
data from slave 4
2
...
6
0-3
...
12-15
data from slave 11
...
data from slave 24
7
0-3
4-7
8-11
12-15
data from slave 31
data from slave 30
data from slave 29
data from slave 28
Flag of the
Execution Control
Address
Bit
Data element
8
0
1
2
3
4
5
6
7
“Config_OK”
“LDS.0”
“Auto_Address_Assign”
“Auto_Address_Available”
“Configuration_Active”
“Normal_Operation_Active”
“APF / not APO”
“Offline_Ready”