AS-i/Modbus Gateway
Connections, Displays and Operating Keys
Subject to reasonable modifications due to technical advance.
Copyright Bihl+Wiedemann, Printed in Germany
Bihl+Wiedemann GmbH · D-68199 Mannheim · Tel. +49-621-339960 · Fax +49-621-3392239 · Internet http://www.bihl-wiedemann.de
is
s
u
e
d
a
te
1
1
.1
.2
0
0
0
26
3 - green, 4 - yellow, 5 - blue, 10 - red
The device in IP65 is powered out of the AS-i line to which it is connected by the elec-
tromechanical interface (penetration technique as it is used with AS-i slaves).
Bus Termination
The RS 485 network can be terminated with resistors by switching on both DIP swit-
ches.
4.3
Display and Operating Elements
On the front panel of the AS-i/Modbus gateway are seven light-emitting diodes, a two-
digit display and two push buttons.
With the devices in IP65 the push buttons are situated inside of the housing to avoid
liquids from entering. The top of the housing has to be screwed off to operate these
push buttons.
4.3.1
LEDs of the Single Masters
power
The master's power supply is sufficient.
ser active
Serial interface communication active via the serial interface.
By AS-i Control an active Control program is shown additionally
with this LED.
config err
Configuration error
At least one configured slave is missing, or at least one detected
slave is not projected or for at least one projected and detected
slave the actual configuration data does not match the nominal
configuration data.
U ASI
The AS-i circuit is sufficiently powered.
ASI active
Normal operation active.
connection of Modbus-
interface on cage clamp
terminal block
and arrangement on
circuit board:
1
PE
2
Shield
3
BUS A
4
BUS B
5
GND
6
PE
7
Shield
8
BUS A
9
BUS B
10
+5V
10
6
7
8
9
1
2
3
5
4
clamp terminal block
buttons
DIP switches