Set_Operation_Mode:
A zero in register 1000 activates the protected mode. All other values switch
on the configuration mode.
Change_Slave_Address:
This function will be executed, if a value is written to register 1002. The val-
ue written is the new address of the slave. The old slaves address must be
written to register 1001 before.
Store_Actual_Parameters:
If a value different to zero is written to register 1003, the actual parameters
(
PI
) will be stored as parameters projected (
PP
).
Store_Actual_Configuration:
If a value different to zero is written to register 1004, the actual AS-i config-
uration will be stored as projected configuration (
PCD
,
LPS
).
Execute_Command:
This function will be executed, if a value is written to register 1006.
The value written will be sent as information-part to a slave, which address
has been written before to register 1005.
The return-values of the functions are accessible in the
exception status
.
packed AS-i Control user memory
Address
Data element
800
800
801
...
862
863
863
high
low
high
...
low
high
low
byte M 0
byte M 1
byte M 2
...
byte M 125
byte M 126
byte M 127
Functions of the
Execution Control
Address
Function
1000
1001,1002
1003
1004
1005,1006
Set_Operation_Mode
Change_Slave_Address
Store_Actual_Parameters
Store_Actual_Configuration
Execute_Command
Further Functions
Address
Function
1007
Disable front panel buttons
1008
Modbus watchdog
1009
Start/stop of control program