background image

5

14.  Connect the distillate outlet of the condenser to a suitable

collection reservoir, using a suitable length of 9mm tubing.

A glass reservoir system is available from Bibby Scientific Ltd.
(Catalogue No. WR20). Please contact the sales office for
details.

15.  Replace the end panel on to the unit.

16.  Take the reservoir control WLS and push the free end of the

rubber tubing onto the nozzle on the left hand end of the unit
- see 

figure 1

.

Use the clip provided to mount the glass pressure bell in the
neck of the distillate reservoir.

Adjust the height of the pressure bell so that the open end is
approx. 140mm below the maximum distillate level.

Electrical installation

THIS EQUIPMENT MUST BE EARTHED!

The electrical installation should be carried out by a qualified
electrician. The following method is recommended.

The equipment is supplied with 1.5m of PVC/PVC flexible, triple
core, circular cable with the following specification, 1.5mm

2

to 

BS 6500 or equivalent and <HAR> or BASEC approved.

The cable gland is designed to accept cable whose diameter is
>7.0mm and <10.5mm. It is recommended that, at the connection
to the mains electrical supply, there is fitted a double pole isolation
switch with a continuous current carrying capacity of 15 amps at
250V, and that overcurrent protection is provided by either a double
pole approved fuse rated at 15A, 250V, or a double pole approved
circuit breaker of similar rating.

These devices should be sited near to the equipment and be clearly
marked “Disconnect  device for ‘Distinction’ Water Still”.

NOTE: Do not connect to electricity supply with 

a 13 amp plug.

Cable connections are shown in 

figures 3a

and 

3b

. Connect to the

line supply noting that the wires in the instrument lead are coloured
in accordance with the following code:

Blue - Neutral
Brown - Live
Green & Yellow - Earth

Mains Cable Replacement

If the mains cable requires replacement, only cable with the
specification given above should be used.

For live and neutral leads use bootlace crimps, size 1.5mm, with a
performance conforming to BS 4G178 part 1, 1984 and part 2,
1986.

For the earth lead use 1.5mm, M4 eyelet crimps with a performance
conforming to BS 4G178 part 1, 1984 and part 2, 1986. A suitable
crimp tool should be used.

Operation

1.  Turn on the cold water supply and adjust the flow to approx.

60 l/hr. Observe that the water flows via the condenser and
into the boiler. Wait until the boiler has attained its correct
operating level and make sure that the excess water is flowing
freely to drain.

2.  Switch on the heating element. The on/off switch is located on

the front panel - see 

figure 1

.

3.  After a few minutes the water will start to boil and distillate

will emerge from the condenser. With new glassware, or after
cleaning, it is advisable to allow this to run to drain for
approximately 30 minutes before beginning collection.

4.   To turn off the still, first turn off the heating element but allow

cooling water to continue for a further 10 minutes to allow the
Still to cool.

WARNING!
Do not use this equipment to distil any liquid 
other than water.

Safety cut-outs

The Distinction Water Still is protected by the following safety cut-
outs:

1.

Reservoir level control

This should be positioned in the collecting reservoir (see
“Assembly”) and turns off the heating element when the
reservoir is full.

2.

Condenser thermostat

Mounted in the condenser’s distillate outlet. Should the water
supply be interrupted steam will begin to emerge from the
condenser causing the thermostat to operate and turn off the
electricity supply to the heating element.

3.

Boiler thermostat

Mounted in the boiler above the heating element. Should the
boiler water level fall and expose the element the thermostat
will operate and turn off the electricity supply to the element.

After operation of either of the thermostats, normal operation may
be resumed by resetting the thermostat by means of their respective
reset buttons mounted on the right hand end panel of the electrical
compartment.

Remove the black plastic cover and then press the red button - a
slight click will be heard if the thermostat had operated.

Before resetting either thermostat the still should be
allowed to cool completely and the cause of the cut-
out operation identified and rectified.

If the thermostats continue to operate, consult a qualified electrician
or the Technical Service Department of Bibby Scientific Ltd.

Summary of Contents for Distinction D4000

Page 1: ...Distinction Assembly and operating instructions Instructions de montage et de fonctionnement D4000 D4000 EURO Water Still Distinction...

Page 2: ...ith or be affected by other equipment with similar qualifications We cannot be sure that other equipment used in its vicinity will meet these standards and we cannot guarantee that interference will n...

Page 3: ...n Water Still can be wall or bench mounted Select a convenient location which has access to the following services Electricity Supply Before connection please ensure that the line supply is suitable T...

Page 4: ...struct access to the thermostat reset buttons see figure 1 5 Take the two metal straps and attach the springs to the rear of the cradles on the stand Place the assembled boiler and element onto the cr...

Page 5: ...d use 1 5mm M4 eyelet crimps with a performance conforming to BS 4G178 part 1 1984 and part 2 1986 A suitable crimp tool should be used Operation 1 Turn on the cold water supply and adjust the flow to...

Page 6: ...SCALING OPERATION REMOVE ANY ACID SPILLS IMMEDIATELY Turn on the water supply and fill the boiler to the normal operating level The water will flush the acid into the boiler The water supply should be...

Page 7: ...Failed electricity supply Restore supply c Thermostat operated Identify and rectify the cause and reset thermostat Water level in boiler a Supply of cooling water is Adjust the supply to is too low h...

Page 8: ...de fr quences radio Il ne doit donc pas interf rer avec d autres appareils r pondant aux m mes directives Ne pouvant tre s r que d autres appareils en fonctionment autour du distillateur soint confor...

Page 9: ...2 i Ins rer les boulons au travers du collier m tallique et le placer autour du tube vas du bouilleur ii Enrouler le collier en fibre et l ins rer entre le tube vas et le collier m tallique Le pliage...

Page 10: ...collier plastique fourni 10 Placer l extr mit libre du tuyau vers l vacuation en s assurant qu il ne pr sente aucun coude pouvant perturber l coulement de l eau 11 V rifier que le robinet du c ntroleu...

Page 11: ...pince sertir est n cessaire Mise en route 1 Ouvrir le robinet d alimentation en eau froide et r gler le d bit 1 l mn environ L eau doit circuler travers le r frig rant Attendre que le niveau d eau dan...

Page 12: ...TECTION DES GANTS ET DES MASQUES FACIAUX DEVRONT ETRE UTILISES LORS DES OPERATIONS DE NETTOYAGE NETTOYER IMMEDIATEMENT TOUTE ECLABOUSSURE D ACIDE Ouvrir l alimentation d eau pour remplir le bouilleur...

Page 13: ...tion du distillat vers V rifier que le tuyau de sortie du vers l vacuation le r servoir se fait mal distillat ne pr sente aucun coude b Event obstru par la sonde du D gager l vent thermostat r frig ra...

Page 14: ......

Page 15: ...Notes...

Page 16: ...f bibby scientific fr www bibby scientific com Bibby Scientific Italia Srl Via Alcide de Gasperi 56 20077 Riozzo di Cerro al Lambro Milano Italia Tel 39 0 2 98230679 Fax 39 0 2 98230211 e mail marketi...

Reviews: