INSTALLATION MANUAL
Parameter
min. max. Default
Personal
Definition
Description
CLS.SLWD.
FORCE
1
99
75
Leaf/leaves force during
closing during slow-down
[%]
Force exerted by leaf/leaves during closing at slow-down speed.
This is the percentage of force delivered, beyond the force stored during
the autoset cycle (and subsequently updated), before an obstacle alarm is
generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current
safety requirements are met with the set value (*). Install anti-
crush safety devices where necessary (**).
BRAKE
0
1
1
Braking
Enables stopping by injecting direct current in the event the safety edge
is tripped
OP SPEED
15
99
99
Opening speed [%]
Percentage of maximum speed that can be reached by motor(s) during
opening.
WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING:
when the display reads “SET”, obstacle detection is not active.
CL SPEED
15
50
50
Closing speed [%]
Percentage of maximum speed that can be reached by motor(s) during closing.
WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING:
when the display reads “SET”, obstacle detection is not active.
OP SLOW
SPEED
15
30
25
Opening slow-down speed
[%]
Opening speed of motor(s) during slow-down stage, given as a percentage
of maximum running speed.
WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING: when
the display reads “SET”, obstacle detection is not active.
CL SLOW
SPEED
15
30
25
Closing slow-down speed
[%]
“Closing speed of motor(s) during slow-down stage, given as a percentage
of maximum running speed.
WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING: when
the display reads “SET”, obstacle detection is not active.
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
(**) Impact forces can be reduced by using deformable edges.
TABELLA “B” - LOGICHE - (LOGIC)
Logic
Definition
Default
Cross out
setting
used
Optional extras
TCA
Automatic Closing
Time
0
0
Logic not enabled
1
Switches automatic closing on
FAST CLS.
Fast closing
0
0
Logic not enabled
1
Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse.
STEP-BY-STEP
MOVEMNT
Step-by-step
movement
0
0
Inputs configured as Start E, Start I,
Ped operate with 4-step logic.
step-by-step mov.
2 STEP
3 STEP
4 STEP
CLOSED
OPENS
OPENS
OPENS
DURING
CLOSING
STOPS
OPEN
CLOSES
CLOSES
CLOSES
DURING
OPENING
STOP + TCA STOP + TCA
AFTER STOP
OPENS
OPENS
OPENS
1
Inputs configured as Start E, Start I,
Ped operate with 3-step logic. Pulse
during closing reverses movement.
2
Inputs configured as Start E, Start I,
Ped operate with 2-step logic. Move-
ment reverses with each pulse.
PRE-ALARM
Pre-alarm
0
0
The flashing light comes on at the same time as the motor(s) start.
1
The flashing light comes on approx. 3 seconds before the motor(s) start.
ENGLISH
SIRIO CBA 230 INV
-
13
D811948_01