INSTALLER WARNINGS

Anything that is not explicitly provided for in the installation ma-

nual is not allowed. The operator’s proper operation can only be 

guaranteed if the information given is complied with. The Firm shall 

not be answerable for damage caused by failure to comply with the 

instructions featured herein.

While we will not alter the product’s essential features, the Firm reserves 

the right, at any time, to make those changes deemed opportune to 

improve the product from a technical, design or commercial point of 

view, and will not be required to update this publication accordingly.

WARNING! Important safety instructions. Carefully read and comply with 

all the warnings and instructions that come with the product as incorrect 

installation can cause injury to people and animals and damage to property. 

The warnings and instructions give important information regarding safety, 

installation, use and maintenance. Keep hold of instructions so that you can 

attach them to the technical ile and keep them handy for future reference.
GENERAL SAFETY

This product has been designed and built solely for the purpose indicated herein. 

Uses other than those indicated herein might cause damage to the product and 

create a hazard.

- The units making up the machine and its installation must meet the requirements 

of the following European Directives, where applicable: 2014/30/EC, 2014/35/

EC, 2006/42/EC, 2011/305/EC, 99/05/EC and later amendments. For all countries 

outside the EEC, it is advisable to comply with the standards mentioned, in ad-

dition to any national standards in force, to achieve a good level of safety.

- The Manufacturer of this product (hereinafter referred to as the “Firm”) disclaims 

all responsibility resulting from improper use or any use other than that for 

which the product has been designed, as indicated herein, as well as for failure 

to apply Good Practice in the construction of entry systems (doors, gates, etc.) 

and for deformation that could occur during use.

- Installation must be carried out by qualiied personnel (professional installer, 

according to EN 12635), in compliance with Good Practice and current code.

- Before installing the product, make all structural changes required to produce 

safety gaps and to provide protection from or isolate all crushing, shearing and 

dragging hazard areas and danger zones in general in accordance with the 

provisions of standards EN 12604 and 12453 or any local installation standards. 

Check that the existing structure meets the necessary strength and stability 

requirements.

- Before commencing installation, check the product for damage.

- The Firm is not responsible for failure to apply Good Practice in the construction 

and maintenance of the doors, gates, etc. to be motorized, or for deformation 

that might occur during use. 

- Make sure the stated temperature range is compatible with the site in which the 

automated system is due to be installed.

- Do not install this product in an explosive atmosphere: the presenc

e of lammable 

fumes or gas constitutes a serious safety hazard.

- Disconnect the electricity supply before performing any work on the system. 

Also disconnect bufer batteries, if any are connected.

- Before connecting the power supply, make sure the product’s ratings match the 

mains ratings and that a suitable residual current circuit breaker and overcurrent 
protection device have been installed upline from the electrical system. Have 
the automated system’s mains power supply itted with a switch or omnipolar 
thermal-magnetic circuit breaker with a contact separation that provide full 
disconnection under overvoltage category III conditions.

- Make sure that upline from the mains power supply there is a residual current 

circuit breaker that trips at no more than 0.03A as well as any other equipment 
required by code.

- Make sure the earth system has been installed correctly: earth all the metal parts 

belonging to the entry system (doors, gates, etc.) and all parts of the system 
featuring an earth terminal.

- Installation must be carried out using safety devices and controls that meet 

standards EN 12978 and EN 12453.

- Impact forces can be reduced by using deformable edges.
- In the event impact forces exceed the values laid down by the relevant standards, 

apply electro-sensitive or pressure-sensitive devices.

- Apply all safety devices (photocells, safety edges, etc.) required to keep the 

area free of impact, crushing, dragging and shearing hazards. Bear in mind the 
standards and directives in force, Good Practice criteria, intended use, the instal-
lation environment, the operating logic of the system and forces generated by 
the automated system.

- Apply all signs required by current code to identify hazardous areas (residual 

risks). All installations must be visibly identiied in compliance with the provisions 
of standard EN 13241-1.

Once installation is complete, apply a nameplate featuring the door/gate’s data.

- This product cannot be installed on leaves incorporating doors (unless the motor 

can be activated only when the door is closed).

- If the automated system is installed at a height of less than 2.5 m or is accessible, 

the electrical and mechanical parts must be suitably protected.

- For roller shutter automation only
  1) The motor’s moving parts must be installed at a height greater than 2.5 m 

above the loor or other surface from which they may be reached.

  2) The gearmotor must be installed in a segregated and suitably protected space 

so that it cannot be reached without the aid of tools.

- Install any ixed controls in a position where they will not cause a hazard, away 

from moving parts. More speciically, hold-to-run controls must be positioned 
within direct sight of the part being controlled and, unless they are key operated, 
must be installed at a height of at least 1.5 m and in a place where they cannot 
be reached by the public.

- Apply at least one warning light (lashing light) in a visible position, and also 

attach a Warning sign to the structure. 

- Attach a label near the operating device, in a permanent fashion, with informa-

tion on how to operate the automated system’s manual release.

- Make sure that, during operation, mechanical risks are avoided or relevant 

protective measures taken and, more speciically, that nothing can be banged, 
crushed, caught or cut between the part being operated and surrounding parts.

- Once installation is complete, make sure the motor automation settings are 

correct and that the safety and release systems are working properly.

- Only use original spare parts for any maintenance or repair work. The Firm dis-

claims all responsibility for the correct operation and safety of the automated 
system if parts from other manufacturers are used.

- Do not make any modiications to the automated system’s components unless 

explicitly authorized by the Firm.

- Instruct the system’s user on what residual risks may be encountered, on the 

control systems that have been applied and on how to open the system manu-
ally in an emergency. give the user guide to the end user.

- Dispose of packaging materials (plastic, cardboard, polystyrene, etc.) in accord-

ance with the provisions of the laws in force. Keep nylon bags and polystyrene 
out of reach of children.

WIRING

WARNING! 

For connection to the mains power supply, use: a multicore cable with 

a cross-sectional area of at least 5x1.5mm

2

 or 4x1.5mm

2

 when dealing with three-

phase power supplies or 3x1.5mm

2

 for single-phase supplies (by way of example, 

type H05RN-F cable can be used with a cross-sectional area of 4x1.5mm

2

). To con-

nect auxiliary equipment, use wires with a cross-sectional area of at least 0.5 mm

2

.

-  Only use pushbuttons with a capacity of 10A-250V or more.
-  Wires must be secured with additional fastening near the terminals (for example, 

using cable clamps) in order to keep live parts well separated from safety extra 
low voltage parts.

-  During installation, the power cable must be stripped to allow the earth wire 

to be connected to the relevant terminal, while leaving the live wires as short 
as possible.  The earth wire must be the last to be pulled taut in the event the 
cable’s fastening device comes loose.

WARNING!

 safety extra low voltage wires must be kept physically separate from 

low voltage wires.
Only qualiied personnel (professional installer) should be allowed to access 
live parts.

CHECKING THE AUTOMATED SYSTEM AND MAINTENANCE

Before the automated system is inally put into operation, and during maintenance 
work, perform the following checks meticulously:
- Make sure all components are fastened securely.
- Check starting and stopping operations in the case of manual control.
- Check the logic for normal or personalized operation.
- For sliding gates only: check that the rack and pinion mesh correctly with 2 mm 

of play along the full length of the rack; keep the track the gate slides on clean 
and free of debris at all times.

- For sliding gates and doors only: make sure the gate’s running track is straight 

and horizontal and that the wheels are strong enough to take the weight of the 
gate.

- For cantilever sliding gates only: make sure there is no dipping or swinging 

during operation.

- For swing gates only: make sure the leaves’ axis of rotation is perfectly vertical.
-For barriers only: before opening the door, the spring must be decompressed 

(vertical boom).

- Check that all safety devices (photocells, safety edges, etc.) are working properly 

and that the anti-crush safety device is set correctly, making sure that the force 
of impact measured at the points provided for by standard EN 12445 is lower 
than the value laid down by standard EN 12453.

- Impact forces can be reduced by using deformable edges.
- Make sure that the emergency operation works, where this feature is provided.
- Check opening and closing operations with the control devices applied.
- Check that electrical connections and cabling are intact, making extra sure that 

insulating sheaths and cable glands are undamaged.

- While performing maintenance, clean the photocells’ optics.
- When the automated system is out of service for any length of time, activate the 

emergency release (see “EMERGENCY OPERATION” section) so that the operated 
part is made idle, thus allowing the gate to be opened and closed manually.

- If the power cord is damaged, it must be replaced by the manufacturer or their 

technical assistance department or other such qualiied person to avoid any risk .

- If “D” type devices are installed (as deined by EN12453), connect in unveriied 

mode, foresee mandatory maintenance at least every six months

- The maintenance described above must be repeated at least once yearly or at 

shorter intervals where site or installation conditions make this necessary.

WARNING! 

Remember that the drive is designed to make the gate/door easier to use and 
will not solve problems as a result of defective or poorly performed installation 
or lack of maintenance

  

SCRAPPING

   

Materials must be disposed of in accordance with the regulations in 
force. Do not throw away your discarded equipment or used batteries 
with household waste. You are responsible for taking all your waste 
electrical and electronic equipment to a suitable recycling centre.

DISMANTLING

If the automated system is being dismantled in order to be reassembled at another 
site, you are required to:
- Cut of the power and disconnect the whole electrical system.
- Remove the actuator from the base it is mounted on.
- Remove all the installation’s components.
- See to the replacement of any components that cannot be removed or happen 

to be damaged.

DECLARATIONS OF CONFORMITY CAN BE FOUND AT http://www.bft-

automation.com/CE

 

INSTRUCTIONS FOR USE AND ASSEMBLY CAN BE FOUND IN THE DOWN-

LOAD SECTION.

D811766_16

Summary of Contents for DEIMOS BT A 600

Page 1: ... ANTRIEB FÜR ZAHNSTANGEN SCHIEBETORE SERVOMOTOR PARA CANCELAS CORREDERAS DE CREMALLERA ACTUATORVOOR SCHUIFHEKKEN METTANDHEUGEL Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully Attention Veuillez lire attentivement les Avertissements qui se trouvent à l intérieur Achtung Bitte lesen Sie aufmerksam die Hinweise im Inneren Atención Leer atentamente las ...

Page 2: ...amentechiusa Porrecuraquandosi azionalosbloccosepresente poichéunatapparella aperta potrebbe cadere rapidamente in presenza di usura o rotture La rottura o l usura di organi meccanici della porta parte guidata quali ad esempio cavi molle sup porti cardini guide potrebbegenerarepericoli Far controllareperiodicamentel impiantodapersonale qualiicato ed esperto installatore professionale secondo quant...

Page 3: ...tomated system breaks down or malfunctions cut of mains power to the system do not attempt to repair or perform any other work to rectify the fault yourself and instead call in qualiied expert personnel professional installer toperformthenecessaryrepairsormain tenance To allow access activate the emergency release where itted Ifanypartoftheautomatedsystemrequiresdirect work of any kind that is not...

Page 4: ...tisation ou sur l installation non prévues dans le présent manuel s adresser uniquement à du personnel qualiié et expérimenté monteur professionnel Une fois par an au moins faire vériier le bon état et le bon fonctionnement de l automatisation par du personnel qualiié et expérimenté monteur professionnel et en particulier tous les dispositifs de sécurité Les interventions de montage d entretien et...

Page 5: ...ehenendirektenEingrifeander AutomatisierungoderderAnlageanqualiiziertes Fachpersonal professioneller Installateur Lassen Sie die Unversehrtheit und den ordnungs gemäßenBetriebderAutomatisierungsowieinsbe sondere der Sicherheitsvorrichtungen zumindest einmal jährlich von qualiiziertem Fachpersonal professioneller Installateur überprüfen DieInstallations Wartungs undReparatureingrife müssen dokument...

Page 6: ... seguridad Las intervenciones de instalación mantenimiento y reparacióndebenserregistradasyladocumentación correspondientesedebemanteneradisposicióndel usuario El incumplimiento de lo antes indicado puede provocar situaciones de peligro DESGUACE La eliminación de los materiales se debe realizar respetando las normas vigentes No desecharsuequipodescartado laspilasolas bateríasusadasconlosresiduosdo...

Page 7: ...t storen Het automatisme niet gebruiken als daarop on derhoudswerkzaamhedennodigzijn Ingevalvan storingofdefectvanhetautomatiseringssysteem het voedingsnet loskoppelen van het automati seringssysteem geen pogingen ondernemen tot reparatieofdirectewerkzaamhedenenzichalleen tot gekwaliiceerd en ervaren personeel wenden professionele installateur voor de noodzakelijke reparatie of onderhoud Om de toe...

Page 8: ...UALE D USO MANOVRA MANUALE USER S MANUAL MANOVRA MANUALE MANUEL D UTILISATION MANOVRA MANUALE BE DIENUNGSANLEITUNG MANOVRA MANUALE MANUEL DE USO MANOVRA MANUALE MANUAL PARA DE USO MANOVRA MANUALE 8 DEIMOS BT A 400 DEIMOS BT A 600 D811972 00100_10 ...

Page 9: ...ere accessibili al pubblico Applicare almeno un dispositivo di segnalazione luminosa lampeggiante in posizione visibile issare inoltre alla struttura un cartello di Attenzione Fissareinmodopermanenteunaetichettarelativaalfunzionamentodellosblocco manuale dell automazione e apporla vicino all organo di manovra Assicurarsi che durante la manovra siano evitati o protetti i rischi meccanici ed inparti...

Page 10: ...sstheyarekeyoperated must be installed at a height of at least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light lashing light in a visible position and also attach a Warning sign to the structure Attach a label near the operating device in a permanent fashion with informa tion on how to operate the automated system s manual release Make sure that dur...

Page 11: ...et que les systèmes de protection et de déverrouillage fonctionnement correctement Utiliser exclusivement des pièces détachées originales pour les opérations d entretien ou les réparations Le Fabricant décline toute responsabilité quant à la sécurité et au bon fonctionnement de l automatisation en cas d utilisation de composants d autres Fabricants Ne modiier d aucune façon les composants de l aut...

Page 12: ...rden Stellen Sie nach der Installation sicher dass der Motor de Automatisierung richtig eingestellt worden ist und dass die Schutzsysteme den Betrieb ordnungsgemäß blockieren Verwenden Sie bei allen Wartungs und Reparaturarbeiten ausschließlich Originaler satzteile Die Firma haftet nicht für die Sicherheit und den ordnungsgemäßen Betrieb der Automatik falls Komponenten von anderen Herstellern verw...

Page 13: ...rado de manera correcta y que los sistemas de pro tección y de desbloqueo funcionen correctamente Usar exclusivamente piezas originales para todas las operaciones de mantenimiento y reparación La Empresa no se responsabiliza de la seguridad y el buen funcionamiento de la automatización en caso que se utilicen componentes de otros fabricantes No realizar ninguna modiicación a los componentes de la ...

Page 14: ...n dat de instelling van het automatiseringssysteem van de motor juist is uitgevoerd en dat de beveiligings en deblokkeringssystemen juist functioneren Uitsluitend originele reserveonderdelen gebruiken voor alle onderhouds of repara tiewerkzaamheden Het Bedrijf wijst iedere willekeurige verantwoordelijkheid af uit veiligheidsredenen en vanwege de goede werking van het automatiseringssysteem als er ...

Page 15: ...tor Montage motor Montaggio accessori trasmissione Mounting drive accessories Montage accessoires transmission Montage Antriebszubehör Montaje de accesorios transmisión Montage accessoires overbrenging Y 50 mm 10mm 25mm 60 70mm A D B E PREDISPOSIZIONE TUBI TUBE ARRANGEMENT PRÉDISPOSITION DESTUYAUX VORBEREITUNG DER LEITUNGEN DISPOSICIÓN DE TUBOS VOORBEREIDING LEIDINGEN 1 2 C 3A 3B 4 3 Y Fissaggio s...

Page 16: ... Lampeggiante Blinker Clignotant Warnblinkleuchte Bombilla Knipperlicht REF SWE SWC SWO 10 L N 11 20 21 41 42 43 50 51 52 60 61 62 70 71 72 73 74 75 S1 S2 S3 FAULT2 FAULT1 PHOT STOP OPEN START BAR H Collegamento di 1 coppia di fotocellule non veriicate per fotocellule veriicate vedere pagine seguenti Connection of 1 couple of untested photocells for tested photocells see the following pages Connex...

Page 17: ...IOMANDO MEMORIZAÇÃO DO RADIOCOMANDO x1 S1 S2 S3 RADIO RADIO RADIO Fisso Steadily lit Fixe Ununterbrochen an Fijo Continu Lampeggio continuo Continuous flashing Clignotement continu Kontinuierliches Blinken Parpadeo continuo Continu knipperen Lampeggio intermittente Intermittent flashing Clignotement intermittent intermittierendes Blinken Parpadeo intermitente Met intervallen knipperen LEGENDA KEY ...

Page 18: ...CP X 37 30 12 CVZ 28 60 X 33 30 8 CVZ S 6 X 40 NO OK N1 39 50 255 120 135 164 287 K L M N P P1 50 25 100 17 2mm O Q S Q1 Q3 Q2 18 DEIMOS BT A 400 DEIMOS BT A 600 D811972 00100_10 ...

Page 19: ...2 50 52 50 51 50 51 50 51 50 51 50 70 72 70 72 73 70 70 72 73 BAR Bar 1 1 2 3 4 5 6 Bar 1 1 2 3 4 5 Bar 2 1 2 3 4 5 Bar 1 1 2 3 4 5 6 6 6 Bar 1 1 2 3 4 5 6 Bar 1 1 2 3 4 5 Bar 2 1 2 3 4 5 Bar 1 1 2 3 4 5 6 6 6 51 51 50 51 50 51 50 52 52 52 74 70 74 70 75 74 70 51 50 70 75 70 74 8 2Kohm 5 SAFETY EDGE SAFETY EDGE DIP2 OFF DIP4 OFF DIP4 ON DIP2 ON DIP3 OFF DIP3 ON 1 BAR 1BAR CL 1 BAR TEST 1 BAR CL TE...

Page 20: ...on 3 PREDISPOSIZIONE TUBI FIG A Predisporre l impianto elettrico facendo riferimento alle norme vigenti per gli impiantielettriciCEI64 8 IEC364 armonizzazioneHD384edaltrenormenazionali 4 PREDISPOSIZIONE FISSAGGIO MOTORE FIG B Predisporre uno scavo dove eseguire la piazzola di cemento dove andranno posizionati i tasselli ad espansione rispettando le quote riportate in FIG B 5 RIMOZIONE CARTER DI CO...

Page 21: ... Dip veriica ingresso costa Dip funzionamento costa OFF OFF OFF Ingresso NC senza veriica inversione in apertura e chiusura BAR OFF OFF ON Ingresso NC senza veriica inversione solamente chiusura in apertura si ottiene lo stop BAR CL OFF ON OFF IngressoNC converiica inversioneinaperturaechiusura BARTEST OFF ON ON Ingresso NC con veriica inversione solamente chiusura in apertura si ottiene lo stop B...

Page 22: ...le fotocellule sono attive sia in apertura che in chiusura Un oscura mento della fotocellula in chiusura inverte il moto solo dopo il disimpegno della fotocellula Attivo solo su FW 3 03 6 Chiusura rapida OFF ON Chiude dopo 3 secondi dal disimpegno delle fotocellule prima di attendere il termine del TCA impostato OFF Logica non attiva 7 Blocca impulsi in apertura OFF ON L impulso di start non ha ef...

Page 23: ...cceso 1s attivazione canale della ricevente radio SET Acceso tasto Set premuto Autoset concluso positivamente Triplice lampeggio Autoset in corso Lampeggio Veloce Autoset Fallito Lampeggiante sincrono con led Radio cancellazione radiocoman di in corso Acceso 1s start stop per attivazione tasto S3 Acceso 10s autoset concluso correttamente 17 PROCEDURA DI REGOLAZIONE Prima dell accensione veriicare ...

Page 24: ...s CEI 64 8 IEC 364 harmonization document HD 384 and other national standards 4 PREPARATION FOR MOTOR MOUNTING FIG B Make a hole in the ground to accommodate the concrete pad with anchors embedded in the base plate for fastening the gearbox assembly keeping to the distances featured in FIG B 5 REMOVING THE COVER Fig C Unscrew the relevant two front screws FIG C rif 1 Push as illustrated FIG C rif ...

Page 25: ...AR CL 8K2 Safety edge input N C If not used leave jumper inserted BAR 8K2 dip Safety edge check dip Safety edge operation dip OFF OFF OFF NC input no veriication reversal while opening and closing BAR OFF OFF ON NC input no veriication reversal only when closing stop when opening BAR CL OFF ON OFF NC input with veriication reversal while opening and closing BAR TEST OFF ON ON NC input with veriica...

Page 26: ... broken during closing movement is reversed only once the photocell is cleared Only active on FW 3 03 6 Fast closing OFF ON Closes 3 seconds after the photocells are cleared before waiting for the set TCA to elapse OFF Logic not enabled 7 Block pulses during opening OFF ON The start pulse has no efect during opening OFF The start pulse has efect during opening 8 3 step logic OFF ON Switches to 3 s...

Page 27: ...et key pressed Autoset completed successfully Flashes three times Autoset in progress Fast lashing 10s Autoset failed Flashing in sync with Radio LED Transmitter deletion in progress Lit 1s Start Stop after key S3 pressed Lit 10s Autoset completed correctly 17 ADJUSTMENT PROCEDURE Before turning the unit on check electrical connections Setthefollowingparameters AutomaticClosingTime motorforce slow...

Page 28: ...ne tranchée où couler une dalle en ciment dans laquelle seront noyés les tirefonds de la plaque de base permettant de ixer le groupe réducteur en respectant les cotes indiquées dans la FIG B 5 RETRAIT DU CARTER DE COUVERTURE Fig C Dévissez les deux vis prévues à cet efet à l avant FIG C rif 1 Poussez de la façon indiquée sur la igure FIG C rif 2 rif 3 pour décrocher le carter des deux petits blocs...

Page 29: ...r dip BAR 8K2 Commutateur dip vériication entrée linteau Commutateur dip fonctionne ment linteau OFF OFF OFF EntréeNF sansvérification inversionàl ouvertureetàlafermeture BAR OFF OFF ON Entrée NF sans vériication inversion uniquement à la fermeture à l ouverture on obtient l arrêt BAR CL OFF ON OFF Entrée NF avec vériication inversion à l ouverture et à la fermeture BAR TEST OFF ON ON Entrée NF av...

Page 30: ...sontactivesenouvertureetenfermeture Unobscurcissement de la photocellule en fermeture inverse le mouvement que lorsque la photocellule est libérée Actif uniquement sur FW 3 03 6 Fermeture rapide OFF ON Se ferme 3s après le dégagement des photocellules avant d attendre la in du TCA coniguré OFF Logique non active 7 Verrouillage impulsions à l ouverture OFF ON L impulsion de démarrage n a aucun efet...

Page 31: ...e Set enfoncée Autoconiguration achevée positivement Clignote trois fois Autoconiguration ou recherche de la butée mécanique en cours Clignotement Rapide 10 s Echec coniguration automatique Clignotante synchrone avec Led Radio Suppression radiocommandes en cours Eclairée 1s Démarrage Arrêt à la suite de l activation de la tou che S3 Eclairée 10 s Coniguration automatique achevée correctement 17 PR...

Page 32: ...I64 8 IEC364 HarmonisierungHD384 sowie die sonstigen nationalen Normen Bezug 4 VORBEREITUNG BEFESTIGUN MOTOR Fig B Legen Sie einen Graben an wo die Zementplatte mit den eingegossenen Ve rankerungenderGrundplattefürdieBefestigungderUntersetzungausgeführt wird und beachten Sie dabei die auf Fig B angegebenen Abmessungen 5 ENTFERNUNG DES SCHUTZGEHÄUSES FIG C Die beiden vorgesehenen Vorderschrauben ab...

Page 33: ... überprüfte DIP Eingang Leiste DIP Funktionswei se Leiste OFF OFF OFF EingangNC ohneÜberprüfung InversionbeiÖffnungundSchließung BAR OFF OFF ON Eingang NC ohne Überprüfung Inversion nur bei Schließung bei Öfnung Anhalten BAR CL OFF ON OFF Eingang NC ohne Überprüfung Inversion bei Öfnung und Schließung BAR TEST OFF ON ON Eingang NC mit Überprüfung Inversion nur bei Schließung bei Öfnung Anhalten BA...

Page 34: ...FF Bei Abdunklung sind die Fotozellen sowohl beim Öfnen als auch beim Schließen aktiv Eine Ab dunklung der Fotozelle beim Schließen schaltet die Bewegungsrichtung erst nach der Freigabe der Fotozelle um Nur aktiv bei FW 3 03 6 Schnelle Schließung OFF ON SchließtdreiSekundennachderFreigabederFotozellen ohnedasEndedereingestelltenTCAabzuwarten OFF Logik nicht aktiv 7 Blockiert Öfnungsimpulse OFF ON ...

Page 35: ...oset erfolgreich abgeschlossen Dreifaches Blinken Autoset läuft Schnelles Blinken 10s Autoset fehlgeschlagen Synchron mit LED Radio blinkend Löschen der Funkbefehle läuft An 1s Start Stop für Aktivierung Taste S3 An 10s Autoset ordnungsgemäß abgeschlossen 17 EINSTELLVERFAHREN Überprüfen Sie vor dem Einschalten die elektrischen Anschlüsse Nehmen Sie die Einstellung der folgenden Parameter vor Zeit ...

Page 36: ...aralasinstala ciones eléctricas CEI 64 8 IEC364 armonización HD384 y otras normas nacionales 4 DISPOSICIÓN FIJACIÓN DEL MOTOR FIG B Disponerunaexcavacióndonderealizarlabasedecementoconlostirafondos delaplacadeapoyoparaijarelgruporeductorrespetandolascotasindicadas en la FIG B 5 DESMONTAJE CÁRTER DE PROTECCIÓN Fig C Desenroscar los dos tornillos frontales especíicos FIG C ref 1 Empujar como se indi...

Page 37: ...proba ción entrada canto Dip funcio namiento canto OFF OFF OFF Entrada NC sin comprobación inversión en fase de apertura y cierre BAR OFF OFF ON Entrada NC sin comprobación inversión solamente en fase de cierre en fase de apertura se logra con el stop BAR CL OFF ON OFF Entrada NC con comprobación inversión en fase de apertura y cierre BAR TEST OFF ON ON Entrada NC con comprobación inversión solame...

Page 38: ...como de cierre Un oscurecimiento de la fotocélula en fase de cierre invierte el movimiento sólo tras la desactivación de la fotocélula Activo sólo en FW 3 03 6 Cierre rápido OFF ON Cierra tras 3 segundos de la desactivación de las fotocélulas antes de esperar que termine el TCA conigurado OFF Lógica inactiva 7 Bloqueo impul sos en fase de apertura OFF ON El impulso de start no tiene efecto durante...

Page 39: ...Set presionada Autoset concluido positivamente Triple parpadeo Autoset en curso Parpadeo Rápido 10s Autoset Fallido Parpadeante sincrónico con LED Radio Borrado radiomandos en curso Encendido 1s Start Stop para activación tecla S3 Encendido 10s Autoset inalizado correctamente 17 PROCEDIMIENTO DE REGULACIÓN Antes de encender comprobar las conexiones eléctricas Conigurarlossiguientesparámetros Tiemp...

Page 40: ...eldendenormen voor de elektrische installaties CEI 64 8 IEC364 harmonisatie HD384 en andere nationale normen 4 VOORBEREIDING BEVESTIGING MOTOR FIG B Een uitgraving voorbereiden om een cement platform uit te voeren met daarin verzonken de ankerbouten van de voetplaat voor de bevestiging van de reductiegroep met inachtneming van de afstanden vermeld in FIG B 5 DE BEKLEDING DEMONTEREN Fig C Draai de ...

Page 41: ... C Indien niet gebruikt de brug niet verwijderen Dip BAR 8K2 Dip veriica tie ingang rand Dip werking rand OFF OFF OFF Ingang NC zonder veriicatie omkering tijdens openen en sluiten BAR OFF OFF ON IngangNC zonderveriicatie omkeringenkeltijdenssluiten stoptijdens openen BARCL OFF ON OFF Ingang NC met veriicatie omkering tijdens openen en sluiten BAR TEST OFF ON ON IngangNC metverificatie omkeringenk...

Page 42: ...jk omgekeerd OFF In geval van verduistering zijn de fotocellen zowel bij opening als bij sluiting actief Door verduistering van de fotocel bij sluiting wordt de beweging omgekeerd na de vrijgave van de fotocel Alleen actief op FW 3 03 6 Vertra gingsafstand OFF ON Sluit 3 seconden na de vrijgave van de fotocellen alvorens te wachten op het einde van de ingestelde TCA OFF Logica niet actief 7 Blokke...

Page 43: ...wachten op gewenste toets 1 s aan Activering kanaal van de radio ontvanger SET Aan Set toets ingedrukt Autoset succesvol voltooid Drie keer knipperen Autoset bezig 10 s snel knipperen Autoset mislukt Knippert synchroon met Radio led Bezig met annuleren van afstandsbedieningen 1 s aan Start Stop activering door toets S3 10 s aan Autoset correct voltooid 17 AFSTELLINGSPROCEDURE Voor het aanzetten de...

Page 44: ...ITALY ...

Reviews: