ENGLISH
TABLE “A” - PARAMETERS MENU - (
PARA
)
Parameter
min.
max.
Default
Personal
Definition
Description
TCA
0
180
40
Automatic closing
time [s]
Waiting time before automatic closing.
t.light
30
300
90
Lighting time of the
courtesy light [s]
Lighting time of the courtesy light [s] Activation time of the courtesy light on the board
output
time
1
240
10
Activation time of
the timed output [s] Activation length of timed radio channel output in seconds
OP.DIST.
SLOUD
7
99
7
Slow-down distance
during opening [%]
Slow-down distance for motor(s) during opening, given as a percentage of total travel.
WARNING: Once the parameter has been edited, a complete uninterrupted opening-
closing cycle is required.
WARNING: when the display reads “SET”, obstacle detection is not active.
CL.DIST.
SLOUD
7
99
7
Slow-down distance
during closing [%]
Slow-down distance for motor(s) during closing, given as a percentage of total travel.
WARNING: Once the parameter has been edited, a complete uninterrupted opening-
closing cycle is required.
WARNING: when the display reads “SET”, obstacle detection is not active.
PARTIAL
OPENING
1
99
20
Partial opening [%]
Partial opening distance as a percentage of total opening following activation of PED pedestrian
command.
OP.FORCE
1
99
75
Leaf force during
opening [%]
Force exerted by leaf/leaves during opening. This is the percentage of force delivered, beyond
the force stored during the autoset cycle (and subsequently updated), before an obstacle alarm
is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current safety requirements
are met with the set value (*). Install anti-crush safety devices where necessary (**).
CLS.FORCE
1
99
75
Leaf force during
closing [%]
Force exerted by leaf/leaves during closing. This is the percentage of force delivered, beyond the
force stored during the autoset cycle (and subsequently updated), before an obstacle alarm is
generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current safety requirements
are met with the set value (*). Install anti-crush safety devices where necessary (**).
OP SPEED
25
99
99
Opening speed [%}
Percentage of maximum speed that can be reached by motor(s) during opening.
WARNING: Once
the parameter has been edited, a complete uninterrupted opening-closing cycle is required.
WARNING: when the display reads "SET", obstacle detection is not active.
CL SPEED
25
99
45
Closing speed [%]
Percentage of maximum speed that can be reached by motor(s) during closing.
WARNING: Once
the parameter has been edited, a complete uninterrupted opening-closing cycle is required.
WARNING: when the display reads "SET", obstacle detection is not active.
Mainte-
nance
0
250
0
Programming num-
ber of operations
for maintenance
threshold
[in hundreds]
Allows you to set a number of operations after which the need for maintenance will be reported
on the AUX output configured as Maintenance or Flashing Light and Maintenance .
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
(**) Impact forces can be reduced by using deformable edges.
TABLE “B” - LOGIC MENU - (
logic
)
Logic
Definition
Default
Cross
out
setting
used
Optional extras
TCA
Automatic
Closing Time
0
0
Logic not enabled
1
Switches automatic closing on
STEP-BY-STEP
MOVEMNT
Step-by-step
movement
0
0
Inputs configured as Start E, Start I, Ped oper-
ate with 4-step logic.
step-by-step mov.
3 STEP
4 STEP
CLOSED
OPENS
OPENS
DURING CLOSING
STOPS
OPEN
CLOSES
CLOSES
DURING OPENING
STOP + TCA
STOP + TCA
AFTER STOP
OPENS
OPENS
1
Inputs configured as Start E, Start I, Ped oper-
ate with 3-step logic. Pulse during closing
reverses movement.
sw mov
Movement on
endstop
0
0
Logic not active
1
Activates the movement reversing when it stops on the endstop
PRE-ALARM
Pre-alarm
0
0
The flashing light comes on at the same time as the motor(s) start.
1
The flashing light comes on approx. 3 seconds before the motor(s) start.
IBL OPEN
Block pulses
during opening
0
0
Pulse from inputs configured as Start E, Start I, Ped has effect during opening.
1
Pulse from inputs configured as Start E, Start I, Ped has no effect during opening.
BOTTICELLI SMART BT A 850-1250 -
21
D813948 03A00_04