ENGLISH
Logic
Definition
Default
Cross
out
setting
used
Optional extras
FIXED CODE
Fixed code
0
0
Receiver is configured for operation in rolling-code mode.
Fixed-Code Clones are not accepted.
1
Receiver is configured for operation in fixed-code mode.
Fixed-Code Clones are accepted.
Protection
level
Setting the
protection level
0
0
A - The password is not required to access the programming menus
B - Enables wireless memorizing of transmitters.
Operations in this mode are carried out near the control panel and do not require access:
- Press in sequence the hidden key and normal key (T1-T2-T3-T4) of a transmitter that has already been memori-
zed in standard mode via the radio menu.
- Press within 10 sec. the hidden key and normal key (T1-T2-T3-T4) of a transmitter to be memorized.
The receiver exits programming mode after 10 sec.: you can use this time to enter other new transmitters by
repeating the previous step.
C - Enables wireless automatic addition of clones.
Enables clones generated with the universal programmer and programmed Replays to be added to the recei-
ver’s memory.
D - Enables wireless automatic addition of replays.
Enables programmed Replays to be added to the receiver’s memory.
E - The board’s parameters can be edited via the U-link network
1
A - You are prompted to enter the password to access the programming menus
The default password is 1234.
No change in behaviour of functions B - C - D - E from 0 logic setting
2
A - You are prompted to enter the password to access the programming menus
The default password is 1234.
B - Wireless memorizing of transmitters is disabled.
C - Wireless automatic addition of clones is disabled. No change in behaviour of functions D - E from 0 logic
setting
3
A - You are prompted to enter the password to access the programming menus
The default password is 1234.
B - Wireless memorizing of transmitters is disabled.
D - Wireless automatic addition of Replays is disabled.
No change in behaviour of functions C - E from 0 logic setting
4
A - You are prompted to enter the password to access the programming menus
The default password is 1234.
B - Wireless memorizing of transmitters is disabled.
C - Wireless automatic addition of clones is disabled.
D - Wireless automatic addition of Replays is disabled.
E - The option of editing the board’s parameters via the U-link network is disabled.
Transmitters are memorized only using the relevant Radio menu.
IMPORTANT: This high level of security stops unwanted clones from gaining access and also stops radio interfe-
rence, if any.
SERIAL MODE
Serial mode
(Identifies how
board is con-
figured in a BFT
network
connection).
0
0
Standard SLAVE: board receives and communicates commands/diagnostics/etc.
1
Standard MASTER: board sends activation commands (START, OPEN, CLOSE, PED, STOP) to other boards.
ADDRESS
Address
0
[ ___ ]
Identifies board address from 0 to
119
in a local BFT network connection.
(see U-LINK OPTIONAL MODULES section)
op.revers.obst
Reversing
obstacle when
opening
0
0
During closure, after an obstacle is detected, the movement gets reversed for 2 seconds.
During opening, after an obstacle is detected, the manoeuvre gets interrupted and the automation is blocked.
1
Both while closing as well as opening, after an obstacle is detected, the movement gets reversed for 2 seconds.
brts
BRTS
0
0
Standard operation with sectional doors (General Notes Ref. Fig. 1 and 2)
1
Operation with tip-up doors, fitted with BRTS accessory (General Notes Ref. Fig. 3)
EXPI1
Configuration
of EXPI1 input
on input-output
expansion
board.
1-2
2
0
Input configured as Start E command.
1
Input configured as Start I command.
2
Input configured as Open command.
3
Input configured as Close command.
4
Input configured as Ped command.
5
Input configured as Timer command.
6
Input configured as Timer Pedestrian command.
7
Input configured as Phot (photocell) safety.
8
Input configured as Phot op safety (photocell active during opening only).
9
Input configured as Phot cl safety (photocell active during closing only).
10
Input configured as Bar safety (safety edge).
11
Input configured as safety Bar OP, safety edge with inversion active only while opening, if while closing the mo-
vement stops.
12
Input configured as safety Bar CL, safety edge with inversion active only while closing, if while opening the mo-
vement stops.
13
Input configured as Phot test safety, tested photocell.
14
Input configured as Phot op test safety, tested photocell active only while opening.
15
Input configured as Phot cl test safety, tested photocell active only while closing.
16
Input configured as Bar safety, tested safety edge.
17
Input configured as safety Bar OP test, safety edge with inversion active only while opening, if while closing the
movement stops.
18
Input configured as safety Bar CL test, safety edge with inversion active only while closing, if while opening the
movement stops.
BOTTICELLI SMART BT A 850-1250 -
23
D813948 03A00_04