Description
5-3
5.3.2
Safety switch-OFF time of the safety channel
The safety switch-OFF time of the safety channel (hard-
ware) is set by means of a jumper. The settings are as fol-
lows:
Jumper 1 bridged: 1 second
Jumper 2 bridged: 3 seconds
Jumper 3 bridged: 5 seconds
If a switch-OFF time of 2 seconds is required, the jumper
must be inserted in position 2 (3 seconds) and the switch-
OFF time of the evaluation channel set by software to 2
seconds (see HB CFC Com1 EN). The shorter switch-
OFF time of the two channels always takes priority.
The safety switch-OFF time during operation (shut-off
time) is also dependent on the software setting (see HB
CFC Com1 EN)!
Summary of Contents for CFC 4000L
Page 2: ......
Page 24: ...Technical data 3 6...
Page 40: ...Transport Installation and Connection 4 16...
Page 45: ...Description 5 5 5 4 1 Image of a BUS system...
Page 46: ...Description 5 6...
Page 48: ...Operation of the Compact Flame Controller 6 2...
Page 50: ...Care and Maintenance 7 2...
Page 52: ...Failures 8 2...