Transport, Installation and Connection
4-13
Contact-
insert
Crimp contact
inner PUR
jacket
outer shielding
outer PUR
jacket
Plastic insert
thread
union nut
single core
15
20
55
4.8.3
Laying the special cable KW6 for standard
housing
No contact chamber may remain bare !
All contact chambers in the contact insert have to be fit-
ted with crimp contacts !
For this purpose use a suitable crimp tool (BFI part No.
8980-4801-00) !
On the flame scanner side the external shielding is con-
nected to the housing mass by means of a clamp con-
nection located between the plastic insert the threaded
part in the cable gland. On the other side the outer
shielding is cut off. The internal shielding is cut on both
sides.