Transport, Installation and Connection
4-9
A
B
tech nolo gy for you r fut ure
Autom at ion
BF I
Typ e
S e r.- No .:
2 4V dc
German y
BF I
Typ e
S er.-
No. :
24 V
dc
Ger m
any
4.7.2
Adaption of the compact flame controller to
the firing installation
Danger to life caused by combustion or explosion !
Incorrect installation or adjustment may result in uncon-
trolled combustion or explosions!
Observe the adjustment instructions of the plant opera-
tor!
Adjustment work may be carried out only by qualified
and approved specialist staff!
All alignments and settings must be carried out, when
new spare parts have been fitted, the compact flame
controller has been moved or the flame image has been
changed (e.g. due to additional fuels, new burners,
changes in the burner/air registers) as well as during all
initial installations!
For selective burner monitoring, the device must be in-
stalled in such a way that the primary combustion zone
in all load ranges is within the visual angle of the com-
pact flame controller. The sighting axis must, if possible,
intersect the first third of the flame of the own burner.
The extension of the sighting axis must not intersect the
first third of the flame of other burners.