Technical data
3-1
3
Technical data
3.1
General characteristic features
Relay loadable with max. 250VAC/1A / 300VA
Current output of the CFC 4000 looped (amplitude)
Additional current output in dependence of the flame
modulation frequency, end frequency adjustable in 16
steps
Additional current outputin dependence of the DC-sig-
nal
Both additional mA outputs adjustable to 0/4 to20mA
Fused loop of the 24 V DC power supply of the CFC
4000
Converts RS232 signals of CFC4000 into RS485 sig-
nals for longer distances (max. 1.200 m).
Network of up to 64 flame monitoring systems with
CFC NET software for operator in control room.
Freely allocatable bus addresses between 0 and 63
Inbuilt BUS termination resistor
Supply voltage selectable between 24 V DC and100-
240 V AC
Long-term data storage on SD card
DIN rail or wall mounting
3.2
Factory settings of the converter 6012
The converter is delivered with the following settings:
Initial value current outputs: 4 mA (DIP 1 = ON)
Current Relay Function (CRF): Off (DIP 2 = OFF)
Sensitivity change-over: Off (DIP 3 = OFF)
BUS termination: Off (DIP 4 = OFF)
Address: 0 (DIP 5/6 = OFF and address switch = 0)
Frequency switch: 60 HZ