Transport, installation and connection
4-10
4.7.1 Handling of the KW5-Shieldings
Outer shielding:
The outer shielding is only connected to the device via the
cable gland. On the loose cable end the shielding should
be cut off short.
Inner shielding:
The inner shielding has to be connected to ground of the
flame amplifier side.
4.8
Storage
Do not unpack any packed flame scanners and accesso-
ries.
The following conditions apply to storage:
•
Store in a dry place. Maximum relative humidity 60 %.
In addition, It has to be assured that the floor in the
storage area will remain dry throughout the storage pe-
riod.
•
Protect from direct sunlight. Storage temperature:
15 °C to 25 °C (59 °F to 77 °F).
•
Store in a dustfree location.
•
Avoid mechanical vibrations and damage.