Technical data
3-1
3
Technical data
3.1
General characteristic features
•
Self-control to verify flawless function of the device
in keeping with European standard EN298 :2012
•
Two spectral bands separately adjustable
•
Selective amplifiering of gas and oil firing systems
•
Si and PbS sensor
•
Fully electronic construction
•
Spectral analyzing process
•
Tested by the German Technical Inspection Associa-
tion TÜV
•
Approved of by DIN DVGW
•
Suitable for safety related applications up to SIL 3 (ac-
cording to IEC 61508)
3.2
Electrical system, optical system, me-
chanical system
Item
Value
Spectral sensitivity
300 to 2700 nm
Angle of view
1°, 2° or 2.7° (UV – IR)
Self-monitoring
fully electronic, 1 x per second
Operating voltage
24 VDC, isolated internally
Current consumption
max. 200 mA
Operating temperature
-20 °C to +70 °C
(-4 °F to 160 °F)
Electrical connection
dust-proof plug-type connector
Type of protection
IP 65
Cable length
Max. 500 m (KW5)
Sight tube connection
1” internal thread ISO 228
Purge air connection
½” internal thread ISO 228
Purge air volume
10 m³/h at standard conditions
Summary of Contents for 2.0GT
Page 2: ...ii...
Page 20: ......
Page 26: ...Technical data 3 6...
Page 38: ...Description 5 2...
Page 40: ......
Page 42: ...Maintenance and servicing 7 2...
Page 44: ...Failures 8 2...
Page 46: ...Order data 9 2...