29
Output Voltage
Distortion:
<4% THD at full linear load.
904 Environment
Operating Temperature:0° to 40° C (32° to 104° F).
0° to 35° C (32° to 95° F) at elevations above 1500 m above sea level.
Storage Temperature:
-15° to 55° C (5° to 131° F).
Relative Humidity:
0% to 90% noncondensing.
High Altitude Operation: Up to 3000 m above sea level; maximum temperature above 1500 m is 35° C (95° F).
Ventilation:
The air around the UPS must be clean, dust-free, and free of corrosive chemicals or
other contaminants. The UPS uses internal fans to circulate the air for cooling. The air
must be free to circulate around the UPS and battery cabinet(s).
905 Protection
Electronic overload and short circuit protection, thermal shutdown, automatic shutdown at low battery voltage,
and overvoltage protection for I/P.
906 Batteries and Battery Charger
Battery type:
Batteries are sealed lead-acid maintenance-free.
Battery AH:
7.2 AH for batteries inside the UPS.
Nominal DC Voltage:
240V.
Recharge Time:
10 hours to 100% after full discharge.
907 Agency Listings and Compliance
U Models: UL listed to UL 1778, CAN/CSA C22.2 No. 107.1 M91. Compliant to FCC Part 15.
E Models: TÜV certified, EN 60950, EN50091-1.
EMC Conformity Declaration: The following devices comply with the EMC standard specifications.
TÜV:(1) Safety: EN50091-1(1996.12)
EMC: EN50091-2 (1995.09)
(1) EMI 1. Conducted noise meets EN50091-2 Table 2.
2. Radiated noise meets EN50091-2 Table 4
(2) EMS
IEC 801-2 level 4.
IEC 801-3 level 3.
IEC 801-4 level 4.
IEC 801-5 level 3.