16
50 or 60 Hz
230 In - 115/230 Out
X2
X4
N-G BOND
See Notes 1, 2, 3.
CAUTION
DIP Switch set to 230*
8E
X1
X3
L2
60 Hz
220 In - 220 Out
(Mexico)
X2
X4
L1
N-G BOND
See Notes 1, 2.
CAUTION
220
DIP Switch set to 220*
8C
X1
X3
L2
50 or 60 Hz
208 In - 208 Out
X2
X4
L1
N-G BOND
See Notes 1, 2, 4.
CAUTION
208
DIP Switch set to 208*
8B
X1
X3
50 or 60 Hz
240 In - 120/240 Out
X2
X4
N-G BOND
See Notes 1, 2, 3.
CAUTION
DIP Switch set to 240*
8A
X1
X3
L2
50 or 60 Hz
220 In - 110/220 Out
X2
N
X4
L1
N-G BOND
See Notes 1, 2, 3.
CAUTION
220
110
110
DIP Switch set to 220*
8D
X1
X3
L2
N
L1
230
115
115
L2
N
L1
240
120
120
Nominal UPS Output Voltage(s)
B6106000
B610010K
104 and/or 208
27.3 amps
48.0 amps
110 and/or 220
27.3 amps
45.5 amps
115 and/or 230
26.1 amps
43.5 amps
120 and/or 240
25.0 amps
41.7 amps
Figure 8: UPS Output Wiring Connections
Find the output wiring configuration (Figure 8A-8E) for your UPS input voltage, frequency, and output
voltage(s). Make the neutral-to-ground (neutral-to-earth) connection first. Then. wire the UPS output as shown.
Notes for Figure 8
NOTE 1: Connect a neutral-to-ground (neutral-to-earth) wire (N-G bond) as
indicated.
NOTE 2: See the table below for maximum output current ratings per phase
(leg).
NOTE 3: For dual-phase outputs with the same voltage, balance the load
current between phases (legs).
NOTE 4: Do not connect loads between L1 and X2/X3 or between L2 and
X2/X3; 104 VAC is present between these points.
*See Section 306 to set the Output Voltage DIP Switch.
Maximum Output Current per Phase (Leg)