900 Specifications
901 Specification Table
* At 0.7 power factor.
** To set output voltage, use the dip switches on the back panel.
902 Bypass
UPS to/from Bypass
Transfer Time:
Zero transfer time.
Auto-reverse:
Returns to normal mode after overload condition removed.
903 AC Output with Nominal Input Power and Loads
Voltage Regulation:
±3%.
Overload Capability:
120% ±10% for 10 seconds.
>130% ±10% for 2 seconds.
Output Frequency:
On utility, same as utility (output is synchronized to input).
On battery, ±0.5% of nominal frequency.
Output Power Factor: 0.7 lag to unity.
Model
6 kVA* / 4.2 kW
10 kVA* / 7 kW
AC Input Voltage:
Maximum Current:
176-276 VAC
(nominal 208, 220, 230, or 240)
25A
176-276 VAC
(nominal 208, 220, 230, or 240)
42A
Output Voltage and
Maximum Output
Current**
208 VAC = 27.3 A
104 VAC = 54.6 A
220 VAC = 27.3 A
110 VAC = 54.6 A
230 VAC = 26.1 A
115 VAC = 52.2 A
240 VAC = 25.0 A
120 VAC = 50.0 A
208 VAC = 48.0 A
104 VAC = 96.0 A
220 VAC = 45.5 A
110 VAC = 91.0 A
230 VAC = 43.5 A
115 VAC = 87.0 A
240 VAC = 41.7 A
120 VAC = 83.4 A
Efficiency (AC to AC) >85% at nominal input voltage (under full load, power factor = 0.7, batteries fully charged).
Acoustic Noise (on
Line Input)
65 dBA typical at 1 meter
55 dBA typical at 1 meter
Typical Standard
Runtime (Minutes)
7 minutes full load.
11 minutes full load.
Weights
B6106000U: 267 lbs. (121 kg)
B6106000E: 201 lbs. (91 kg)
Battery Cabinet, no batteries: 27 kg (59.5 lbs.)
Battery Cabinet, 1 string: 76 kg (167.6 lbs.)
Battery Cabinet, 2 strings: 125 kg (275.6 lbs.)
B610010KU: 518 lbs. (235 kg)
B610010KE: 396 lbs. (180 kg)
Battery Cabinet, no batteries: 69 kg (152.1 lbs.)
Battery Cabinet with batteries: 365 kg
(804.7 lbs.)
Dimensions
(H x W x D)
UPS: 37.8 x 13.4 x 25.6 in.
(960 x 340 x 650 mm)
Battery Cabinet: 37.8 x 15 x 27.25
960 x 380 x 690
B6106000U: 31.5 x 10.3 x 21.9 in.
(800 x 260 x 555 mm)
B6106000E and Battery Cabinet:
27.8 x 10.3 x 21.9 in.
(705 x 260 x 555 mm)