BEST 510
Appendix A
28
ADVANCED COMMUNICATIONS
10 Second Test:
Computer:
T<cr>
UPS:
Test for 10 seconds and return to utility.
If battery low warning occurs during testing, the UPS will return
to AC utility immediately.
Test until Battery Low:
Computer:
TL<cr>
UPS:
Test until battery low and return to utility.
Test for Specified Time Period:
Computer:
T<n><cr>
UPS:
Test for <n> minutes
(a)
During testing, UPS returns to utility immediately if
battery low occurs.
(b)
<n> is a number ranging from 01 to 99.
Shutdown Command:
Computer:
S<n><cr>
UPS:
Shut UPS output off in <n> minutes
(a)
The UPS output will shut off in <n> minutes, even if
the utility is present.
(b)
The UPS may shutdown in less than <n> minutes due
to low battery.
(c)
After UPS shutdown, the UPS controller monitors the
utility. If the utility is present, the UPS will wait for
10 seconds before restarting.
(d)
<n> is a number ranging from 2., ..3., ..01, 02.., to 10.
For example S 3 <cr> = shut output off in (3) minutes