Be42 OEM's Manual V5.0.XX - December - 2010 page 9
9
4.30 LOG EVENTS
To have access to the LOG (Memory) events follow the instructions:
- Push the [OFF] button
- Remove the power supply
- Push and hold the [STOP] button; in the same time apply the Vdc supply (battery)
- When display turns on, release the [STOP] button
- Using [
←F8] and [F9→] you can browse the events E01 up to E100
- Push the [STOP] button to display the code of the EVENT (see table 4.10)
- To quit the LOG EVENTS, remove the power supply
Note: to cancel the LOG EVENTS push [
←F8] and [F9→] simultaneously until the display blinks.
Section 5.0 LED indicators
5.1 Lamp and Display Testing
To test the LEDs and DISPLAY push the [OFF] pushbutton; the display turns off (OFF mode). Push and hold
the
[←F8] and [F9→] pushbuttons simultaneously. The LEDs and DISPLAYs remain energized as long as the
pushbuttons are pressed and held together.
Section 6.0 Programming and Reading Parameters
We recommend that you use the BE42-SCADA software for programming. You can also program the controller
by using the pushbuttons on the front fascia. The 4-digits display indicates the code of a parameter and its
setting. Section 7.0 lists all parameters. To enter the Programming Mode, use the following instructions. To use
a password see sections 6.40, 6.50 and 6.60.
6.10 Enter the Programming Mode
1) -
Provide a voltage from a battery supply of
over 11.5V
. Push the [OFF-F7] pushbutton to enter the OFF
mode; the LEDs and display turn OFF (the dot on the right side of the display will start to blink)
2) -
Push and hold the [
F9→] and [ACK-F10] pushbuttons simultaneously for about 5 seconds, until the yellow
Led [h/Prog.] starts to blink. When the display indicates [ProG], release the buttons.
3) -
If the Be42 is
password protected
(*), the messages [PASS] and [42.42] will appear in sequence; you are
required to follow the instructions of Table 6.11. If the Be42 is
not password protected
, the programmable
parameter [P.0] will be displayed and the Be42 is ready for programming (section 6.12, step-2).
(*) Note: the password consists of 2 groups of digits ranging from 0 to 99. Example: [12.34]; 12 is the 2-digit code on
the left, and 34 is the 2-digit code on the right.
TABLE 6.11: Enter the PASSWORD
1) -
Push [TEST] or [AUTO] in order to choose the proper code (between 00 and 99, except 42).
2) -
Push
[F9
→] to select the 2 digits on the right side.
3) -
Push [TEST] or [AUTO] in order to choose the proper code (between 00 and 99, except 42).
4) -
Push [ACK-F10] to confirm the password; if the password is ok, the Be42 will indicate [P.0] and the unit is ready
for programming. If the password is wrong, the display will indicate [4242] and you are required to insert the correct
password.
If you lose the password, the unit must be returned for service.