Be42 OEM's Manual V5.0.XX - December - 2010 page 18
18
7.11 - Temperature Sensor
7.12 - Fuel Level Sensor
Display
Parameter
Default
Range
Display
Parameter
Default
Range
[°C1]
Temperature
[ 128]
0°C up to
250°C
0 Ohm up
to 2000
Ohm
[FUE1]
Fuel Level
[ 0 ]
0% up to
99%
0 Ohm
up to
2000
Ohm
[-r1-]
Resistance
[ 19 ]
[-r1-]
Resistance
[ 10]
[°C 2]
Temperature
[ 115]
[FUE2]
Fuel Level
[ 20]
[-r2-]
Resistance
[ 26]
[-r2-]
Resistance
[ 50]
[°C 3]
Temperature
[ 90]
[FUE3]
Fuel Level
[ 50]
[-r3- ]
Resistance
[ 46]
[-r3-]
Resistance
[ 100]
[°C 4]
Temperature
[ 80]
[FUE4]
Fuel Level
[ 80]
[-r4- ]
Resistance
[ 67]
[-r4-]
Resistance
[ 150]
[°C 5]
Temperature
[ 70]
[FUE5]
Fuel Level
[ 90]
[-r5- ]
Resistance
[ 95]
[-r5-]
Resistance
[ 200]
[°C 6]
Temperature
[ 40]
[FUE6]
Fuel Level
[ 99]
[-r6- ]
Resistance
[ 287]
[-r6-]
Resistance
[ 250]
Section 8.0 - Alarms, Warnings and Shutdowns
The Be42 features Shutdowns (the engine stops) and Warnings (the engine will continue to run) and provides:
A)
- a general indication of alarm presence by means of the message [ALAr.] on the display
B)
- 4 configurable outputs for specific alarm indication with more than 40 options (see 7.08 and 7.09)
C)
- symbols on the front panel to indicate the most important alarms
D)
- display messages indicating warnings and shutdowns (see Table 4.1)
E)
- a pushbutton to silence the Horn ( [ACK-F10] )
Terminal #6 is pre-configured for HORN output (Option 39). A relay and a HORN should be externally provided.
To silence the HORN, push the [ACK-F10] pushbutton or wait for the
[P.50]
to expire (see section 7.05). If the
[P.50]
is set to
[OFF]
, the only way to silence the Horn is by means of the [ACK-F10] pushbutton.
To browse the alarm
memory push the [→F9] pushbutton. To display alarm details, push the [←F8] pushbutton.
To clear the alarm from the panel, remove the cause of the alarm and then press the [OFF] pushbutton. Table
4.10 in the section 4.0 indicates all alarms.
Section 9.0 Hour Meter
To clear or pre-load the counter, use the following instructions:
1) -
Enter the programming mode as indicated in sections 6.10 & 6.20
2) -
Select the parameter [P.51] by means of the
[←F8] or [F9→] pushbutton.
3) -
Press the [START-F1]
and [TEST ↑] to set a value. If you set [0], you will cancel the [h-counter]. If you set a
value between 1 and 50000, you will pre-set the counter. Follows steps 4A) or 4B) according to your needs.
4A) -
Press and hold the [ACK-F10] and
[F9→] pushbuttons simultaneously until the [SaVE] message appears
(for about 5 seconds); the Be42 saves the hour counter in the memory and will enter the OFF mode.
4B) -
Press the [OFF] pushbutton to exit the procedure without modifying the counter.