12.2 - Calibrating a measurement
(Note: to exit the procedure push the [OFF] pushbutton at anytime)
1) -
Press the
[←F8] or [F9→] pushbutton to select a 'Parameter name' (see Table 12.2).
2) -
Press the [ACK-F10] pushbutton to display the reading of the measurement (example 395V).
3) -
Press the [TEST ↑] (or [AUTO ↓]) to adjust the reading according to an external reference (example 400V).
4) -
When finished, push the [ACK-F10]
again to display the 'Parameter name'. Select another 'Parameter
name'
to calibrate by pushing the [←F8] or [F9→] pushbutton.
When finished, you have 3 options: 5A, 5B or 5C.
5 A ) -
Exit the procedure without saving by pushing the [OFF] pushbutton.
5 B ) -
Restore the factory default calibration: press and hold the
[←F8] and [F9→] pushbuttons simultaneously
until the display blinks twice. You are required to save the setting as indicated in step 5C).
5 C ) -
Save the calibration: push and hold the [ACK] and
[F9→] pushbuttons simultaneously until the [SAVE]
message appears (approximately 5 seconds); the Be42 saves the calibrations and remains in Manual mode.
Table 12-2, List of the Measurements
'Parameter'
Description
Unit
Recommended Calibration Range
[n1.n2]
Mains Voltage phase L1-L2
Volt
300 up to 400Vac
[n2.n3]
Mains Voltage phase L2-L3
Volt
300 up to 400Vac
[n1.n3]
Mains Voltage phase L1-L3
Volt
300 up to 400Vac
[FrEq]
Frequency (Mains/Generator)
Hz.
45 up to 55 Hz
[L1.L2]
Generator Voltage L1.L2
Volt
300 up to 400Vac
[Curr]
Generator Current
Amp
4 up to 5Aac (C.T. output)
[bAtt]
Battery voltage
Vdc
Voltage of the battery
[bAr] (°)
Oil Pressure
Bar
2 Bar up to 4 Bar
[°C] (°)
Engine Temperature
°C
80°C up to 100°C
[FUEL] (°)
Fuel Level
%
80% - 90%
(°)Note: in order to obtain a reading on display you are required to set a value in P29, P30 and P38
12.3 - To clear the Memory
note: you are required to stop the engine before clearing the memory
-
Remove the supply. Push and hold [I-F3] & [I-F5] pushbuttons simultaneously and apply the Vdc supply.
-
Push the pushbuttons according to the message that appears on display (in a sequence)
- After pushing the last pushbutton [AUTO], the message [-EPP] will appear
- Remove the supply and re-program the controller according to yur need. We recommend to program a
passsword in order to limit the access.
Section 13.0 Troubleshooting Guide
The Basic Troubleshooting Guide is intended to provide you with a guide to problems that you may experience
with the Be42.
We recommend that you disconnect the unit from the panel and set up the troubleshooting
application circuit as indicated in section 13.1. This procedure should be carried out by qualified personnel only.
To exit the Troubleshooting, remove the Vdc supply at anytime