15
initial setup process of the controller (when power is connected
or when the controller’s reset operation is performed).
1. Operation Volume:
Make sure that the controller is configured for Volume operation
as described in the BASIC SETTINGS chapter at the beginning
of this document.
Once a Volumetric operation is set on the first setup screen,
press the
icon to move to the next water meter setting
screen. This screen allows the user to set the following water
meter parameters:
High Flow Rate (H.F.R.) - indicated by the on-screen
icon.
This parameter defines the minimal allowed time between two
water meter pulses. When pulses are received in shorter interval
than this parameter a High Flow indication is presented by the
controller and the operation stops. (See the fault messages
paragraph in the monitoring chapter below.) The factory default
is 60 seconds; use the
and the
buttons to set the required
H.F.R. parameter.
Press the
button to move to the next water meter
setup parameter.
Timer Override (T.O.R.) - indicated by the on-screen
icon.
This parameter defines the maximal allowed time between two
water meter pulses. When pulses are received in longer interval
than this parameter a water meter malfunction indication is
presented by the controller and the operation stops. (See the fault
messages paragraph in the monitoring chapter below.)
The factory default is 10 minutes; use the
and the
buttons
to set the required T.O.R. parameter.
Press the
button to move to the next water meter
setup parameter.