Programming Steps
This chapter describes the required programming steps of the
controller and it is divided into three sections: Basic Settings,
Pressure management settings, and end of line flushing settings.
Basic Settings:
First Basic Settings Screen
The basic controller setting should be done once the controller is
wired to the system and the power is connected, or after a total
reset operation is performed. The first setting screen appears
displaying 3 optional settings:
1. Solenoid Type:
Upon initial start-up the connected solenoid type is checked by the
controller; it must be a DC latch solenoid.
2. Clock Mode:
Press the
bbutton and set the system clock to 12 or 24 hour
clock. Factory default - 24h.
3. Time / Volume Operation:
Press the
button and select the required operation mode. Select
TIME for BERMAD’s pressure management by time application.
Note the icons change according to your selection: the icon should
be selected for time operation. Factory default - Time.
Press the
button to move to the next basic settings screen.
Second Basic Settings Screen
In the second setting screen the operator can set the Flow Switch
usage mode. Please note that a flow switch can be used only for
BERMAD’s pressure management by time intervals application.