11
Programming Steps
Basic Settings:
Setting Flow Reference Set-point
Upon entering to this screen the display
shows the [SP:PH] (Set Point : Pulses per
Hour) title.
Use the
or the
buttons to set
the flow-rate value by number of pulses
per hour. This is the flow-rate that
distinguishes between high and low
pressure conditions.
Please note:
The flow reference entry ranges between 0 and 9999 pulses/hour.
The factory default value is 50 pulses per hour.
Press the
button to move to the next screen.
Setting the Low to High flow stabilization delay timer
Upon entering to this screen the display
shows the
[SP:tH]
(Set Point : High flow timer) title.
Use the
or the
buttons to set the
required delay time parameter which is
used for verifying that the change from
LOW flow to HIGH flow is stable.
Please note:
The timer values range between 0 and
60 minutes in 1 minute steps.
The factory default value is 1 minute.
Press the
button to move to the next screen.
Fig.1
- Flow set-point
Fig.2
- High flow timer