24
and the operation stops. (See the fault messages paragraph in the
monitoring chapter of this document.) The factory default is 60
seconds; use the
and the
buttons to set the required H.F.R.
parameter.
Press the
button to move to the next water meter
setup parameter.
Timer Override (T.O.R.) - indicated by the on-screen
icon. This
parameter defines the maximal allowed time between two water
meter pulses. When pulses are received in longer interval than
this parameter a water meter malfunction indication is presented
by the controller and the operation stops. (See the fault messages
paragraph in the monitoring chapter of this document.) The factory
default is 10 minutes; use the
and the
buttons to set the
required T.O.R. parameter.
Press the
button to move to the next water meter setup
parameter.
Fill-Up Time (F.U.T.) - indicated by the on-screen
icon.
This parameter defines the time it takes to fill-up the system pipes
at the beginning of the valve operation. During this time the system
does not enter to High Flow fault. In purging systems where the
purged water is released by open-end pipe to the atmospheric
pressure, the flow rate can be high. Make sure that the F.U.T. and the
H.F.R. parameters are correctly set for your system requirements. The
F.U.T. factory default value is 6 minutes and it can be changed by the
and
buttons.
Press the
button to move to the next programming screen.
Move to the Operation length programming screen, this is the screen
with the blinking
icon, the blinking triangle with the digit 1 in it,
and the XX icon. Use the XX and the
icon. Use the
buttons to