Part 7
Temporary manual control mode:
Activation:
1. The "
" select key must be pressed briefly (< 1 sec.).
2. The red LED(s) of output channel 1 (4-channel operation) resp. 1/3 (2x2-channel
operation) in the LED array start flashing. The actuator is now temporarily in the
manual control mode, control from the EIB is disabled and all output channels are
stopped. The red LED beside the select key is off!
Operation:
A short press (< 1 sec.) of the "
" key selects the output channel which is to be
controlled manually. The two status LEDs (
) of the output selected in the LED array
start flashing. Pressing the select key repeatedly permits switching between the outputs
and terminating the temporary manual control mode (A1
→
A2
→
A3
→
A4
→
End). If the
actuator works in the 2x2-channel mode, the outputs are combined automatically and
controlled in common. (A1 / A3
→
A2 / A4
→
End). After termination of the manual control
mode, the actuator goes back to 'normal' bus operation. The "
" and "
" keys can be
used to control the selected output channel and to modify the switching status and the
sense of movement. The LEDs beside the keys indicate the switching state of the
selected channel. The switching states of non selected outputs are indicated as for
'normal' bus operation by means of the LEDs of outputs A1 thru A4 in the LED array.
Deactivation: - if no further key is pressed after more than 5 seconds, or
-
- when the select key is pressed once again after all outputs channels have been selected
once with the key, or
-
- by bus reset or reapplication of bus voltage (bus voltage return) or
-
- by switching off the mains voltage.
If the "
" key is pressed in the temporary manual control mode for at leat 5 seconds, the actuator
changes over to permanent manual control. Pressing the "OFF" key in the temporary manual control
mode yields no reaction!
On activation of the temporary or permanent manual control mode, all output channels are generally
stopped and active safety functions are aborted. Output channel control via the bus is disabled.
Safety functions are reactivated after deactivation of the manual control mode, if they have not been
cancelled
(cf. "Safety function")
.
Manual control mode enable:
The manual control mode is available only when mains voltage is present. The manual control mode
generally can be disabled by selecting the parameter "Manual control = disabled" on the "Manual control"
card. Depending on the "Manual control on bus voltage failure" parameter, it is possible to specify in
addition (with manual control generally disabled) whether a manual control is to be permitted even in the
event of bus voltage failure. An activated manual control mode is terminated on return of bus voltage.
Manual control mode information:
•
The parameterized "Break during change of movement direction" is taken into account also for the
manual control mode.
•
In the manual control mode, only long operation (MOVE) (long depression of key) and a stop command
(short depression of key) are possible. When delivered ex factory (actuator not yet programmed), the
long operation (MOVE) is factory-adjusted to 'infinite'. After programming of the device with the ETS, the
moving time parameterized for each output channel under "Long operation (MOVE)" is applicable.