Shutter actuator 4gang 6A 230V manual
RMD
75314013
Technical
Documentation
© Gebr. Berker 2005
Version: 10.05.2005
Page: 3 / 17
(Subject to prior change)
75314013.doc
Part 7
Connection diagram:
Assignment of terminals:
L1
L2
L3
N
A3
A 4
N
A1
A 2
M1
M2
A1
A2
A3
A4
OFF
L
L
L
L
L
L
red
black
instabus-
wire
Hardware information:
•
The supply voltage (mains voltage) is connected to terminals N and L beside the terminals of output A1.
Output A1 and thus motor M1 are then supplied at the same time.
The supply of outputs A2 thru A4 requires an additional phase conductor connected to the respective L
terminals.
It is not necessary to connect a motor to output A1. For proper functioning of the device, connection of
the mains voltage (terminals N and L) is, however, necessary.
•
Connection of different phase conductors is possible.
•
If motors are to be connected in parallel to an output, it is absolutely indispensable to observe the
corresponding instructions of the motor manufacturers to avoid irreparable damage to the motors. If
necessary, use supplementary isolating relays.
•
Use only shutters with end position limit switches (mechanical or electronic). The limit switches of the
motors connected must be checked for correct adjustment.
•
Activation of the manual control mode stops all output channels. In this case, bus communication has no
longer any effect on the relay switching states. Safety movements will be aborted. A safety function will
be subsequently executed on leaving the manual control mode, if still active. In the manual control
mode, only long operation (MOVE) (long depression of key) and the stop command (brief depression of
key) are available.