33
Nr.
Parameter name
Factory
setting
Lower
limit
Upper
limit
Description
17
CH1 max. Temp.
80°C
10°C
80°C
Max. settable value for high system
18
CH1 min. Temp.
50°C
10°C
Par.1
Min temp. value high system (at max. external T.).
19
CH1 ON diff.
7°C
0°C
20°C
Burner re-ignites after said differential.
E.g.: 70°C – 7°C = 63°C
20
CH1 OFF diff.
3°C
0°C
20°C
The burner goes out after said differential.
E.g.: 70°C+3°C= 73°C
21
CH1 attenuation
0°C
0°C
70°C
Ch1 temp. attenuation (par.1) only if the high tempera-
ture system thermostat is on.
22
CH2 adjustment
1
0
3
0 = Temperature at fixed point.
1 = Weather with probe outside
2 = 0–10V: power (Acts on power)
3 = 0-10V:temperature (Acts on temperature)
23
CH2 max. Temp.
50°C
10°C
70°C
Max. set heating value low system.
24
CH2 min. Temp
25°C
10°C
Min temp. value low system (at max. external T.)
25
CH2 attenuation
0°C
0°C
70°C
Ch2 temp. attenuation (par.3) only if the low tempera-
ture system thermostat is on.
26
CH2 ON diff.
5°C
0°C
20°C
Burner re-ignition differential below low temp. system
setpoint
27
CH2 OFF diff.
3°C
0°C
20°C
Burner burn out differential exceeding low temp. sys-
tem setpoint
28
Mix valve on time
5 sec
0 sec
255 sec Mixer valve opening time
29
Mix valve off time
7 sec
0 sec
255 sec Mixer valve closing time
30
Mix valve stop T
5 sec
0 sec
255 sec Mixer valve stand-by time
31
Mix valve on-off diff
2°C
0°C
30°C
Mixer valve open/closed differential
32
Mix valve stop diff.
2°C
0°C
30°C
Mixer valve stand-by differential
33
Power control
1
0
1
0 = power distributed over min. number burners
1 = power distributed over max. number burners
34
Pump mode
0
0
1
Third pump setpoint:
0 = Main pump of system/loop
1 = Low temperature pump
35
Anti-freeze
3°C
-30°C
15°C
Initial temp. for frost protection (NB1)
36
Gas type
1
1
7
1 = Methane with exhaust flue < 15m
2 = Methane with exhaust flue > 15m
3 = LPG with exhaust flue < 15m
4 = LPG with exhaust flue > 15m
5 = Town Gas
6 = Gas F
7 = Gas G
37
Min. outside T.
0°C
-20°C
30°C
Min external temperature (provides max. flow tempera-
ture value setting)
38
Max outside T.
18°C
0°C
30°C
Max external temperature (provides min. flow tempera-
ture value setting)
38.
Outdoor Temperature
summer/winter function
0°C
0°C
30°C
Outdoor temperature above which heating circuit
requests are deactivated
0= function not activated
39
Correction Text
0°C
-30°C
30°C
External temperature corrector factor
40
Emergency T.
70°C
10°C
80°C
Emergency temperature of slave if the Master breaks
down.
41
Parameter reset
0
0
1
1 = Slave reset to factory parameters.
N.B. Parameter 36 (gas type) is not changed by reset-
ting factory parameters
42
Flowmeter
1
0
1
0 = slave fails to check the flowmeter
43
Protocol
1
0
1
0 = Eco protocol
1 = Argus link
PARAMETER 35 - FROST PROTECTION
The third pump will start up if the outside temperature is lower than parameter 35 (Frost protection) or if the flow tem-
perature is lower than 5°C. If after 10 minutes the T1 fails to exceed 5°C, a burner will start up at maximum power until
T1 exceeds 20°C. If after 10 minutes the T4 is still below parameter 35 but T1 exceeds 5°C the pump will work until T4
exceeds parameter 35.