8
4 INSTALLATION
b
Power Plus Box P INT-EXT
heating units must be in-
stalled in conformity to the latest provisions of the
law and standards in force concerning heating units,
condensing boilers and/or other applicable regulato-
ry provisions.
4 .1 Product packaging and
identification
The
Power Plus Box P INT-EXT
heating unit is supplied,
packed and protected by a strapped carton.
Figure 5
1
Boiler
2
Control panel
3
EC marking/Symbol cartouche
4
Packaging
5
Polyester corners
6
Polyester protection panel
7
Strap
Details of the product are written on the outside: model,
power, version and type of fuel. Contact your local dealer in
case of any differences with the order.
Ensure the goods are intact and complete after unpacking
them.
b
Do not leave the packaging within the reach of chil-
dren as it could be a potential source of danger.
The tag on the front side of the boiler’s electrical board,
contains the following information:
- Product name
- Serial number
- Product identification code
- CE certification number
- Gas type and pressures from mains
- Power type from mains
- Rated heat capacity (Qn)
- Rated working power (Pn)
- Efficiency according to 92/42/EEC Directive
(η)
- Max pressure and temperature (Pms)
- Primary system (T)
- NOx class (NOx)
Figure 6
a
It is forbidden to remove or mishandle the identifica-
tion plates, markings and any other making it difficult
to safely identify the product.
4 .2 Installation premises
The heating unit must be installed in premises used exclu-
sively for the latter conforming to standards and legislation
in force and where combustion exhaust products and com-
bustion air intake is conveyed out of said premises. Where
combustion air is instead taken from the installation prem-
ises then the latter must be equipped with suitably sized
vents conforming to standards.
b
The space required to reach the safety and adjust-
ment devices and to carry out maintenance must be
considered. We recommend leaving a space of at
least 500 mm at the back of the appliance.
b
Ensure that the degree of the heating unit’s electrical
protection is compatible with the characteristics of
the installation premises.
b
Electrical parts must be placed at a height of no less
than 500 mm from the ground where heating units are
supplied with fuel gas with specific weight exceeding
that of air.
b
Heating units may not be installed out in the open
(unless they are not specific outdoor units).
b
The heating unit is equipped with a frost protection
function, useful for installations where the tempera-
ture of the environment could be below 0°C. Gas and
electricity must be supplied for this system to work,
apart from a correctly pressurized water circulation
system and the system must not be in shutdown due
to any type of error.