11
If you decide to bring together in one manifold the dis-
charges of each unit, the diameter of the pipe to be used
for one or two units
Power Plus Box P INT-EXT
series con-
nected in series is Ø200 mm (see Figure 8). For cascade
installations where there are more than two machines the
diameter of the exhaust manifold must be properly sizing,
or simply connect up to two
Power Plus Box P INT-EXT
using
multiple lines Ø200 separated.
Maximum Pipe Length (m)
Installed power
(kW)
with Ø 160
with Ø 200
230
60
-
345
60
-
460
40
60
575
25
60
690
-
60
805
-
55
920
-
40
1035
-
35
1150
-
25
Figure 8
5 INSTALLATION DIAGRAMS
An installation diagram must generally be adapted to the
manufacturing characteristics of the relevant heating unit,
with the purpose of exploiting the boiler potentials to the
full and maintain the entire installation efficient for as long
as possible.
The Figure 9 is shown an installation without a mixing el-
ement, in Figure 10 is shown a installation with a mixing
element.
Figure 9
Figure 10