ENGLISH

MINIMUM POWER ADJUSTMENT (P. LL)

-  Turn the domestic hot water temperature selector till LL is shown

Taking care not to press on the inner shaft

, turn the 

red do-

mestic hot water minimum adjustment screw 

with a screw-

driver until the pressure gauge reads the value indicated in the 

multigas table.

MAXIMUM HEATING ADJUSTMENT POSSIBILITY (P. 23)

Check that the pressure read on the pressure gauge corresponds 

to that shown on the multigas table. 

If it does not, carry out the adjustment operations described below:

-  turn the domestic hot water temperature selector till 23 is shown. 

Wait for the boiler to start

-  press ENTER to access the parameter modification function

-  turn the domestic hot water selector until the pressure gauge 

corresponds to that indicated in the multigas table

The boiler has already been factory adjusted by the manufacturer. 

For LPG gas: the boiler has been regulated in I3B/P category (G30). 

If  you  need  to  regulate  in  I3+  or  I3P  categories  (G31)  exclude 

pressure regulator.

If a new adjustment is required, for example, after extraordinary 

maintenance, replacing the gas valve or converting from natural 

gas to LPG, proceed as follows.

 

Maximum and minimum power, minimum and maximum 

heating, must be adjusted in the indicated sequence by 

qualified staff.

-  unscrew the lower cover fixing screw (

C

, fig. 3c)

-  Pull the cover towards you and remove (

A-B

) (fig. 4a) 

-  Loosen the two fixing screws (

D

) and remove the shell (fig. 3a

)

-  Lift up the panel and turn it forwards

-  Loosen the pressure tap screw downline from the gas valve by 

about two turns and connect the pressure gauge to it

-  Carefully prise out the cap protecting the adjustment screws 

with a screwdriver

  CALIBRATION & SERVICE operations must be performed 

with the boiler in the OFF position. To do this, press the 

 

button until the display shows “- -” (fig. 40).

  During  parameter  modification  operations,  the  “select  fun

-

ctions” button acts as an ENTER (confirm) button, the 

 but-

ton acts as an ESCAPE button. If no confirmation is given 

within 10 seconds, the value is discarded and returns to the 

previously set one.

Setting the password

Press and hold down the operating mode button and the   button 

together for about 10 seconds. The display will look like fig. 41.

Enter  the  password  for  accessing  the  parameter  modifications 

function by turning the domestic hot water temperature selector to 

the required value.

The password is located on the back side of the control panel. 

Confirm by pressing ENTER.

Calibration phases

Turn the domestic hot water selector to sequentially scroll the CA

-

LIBRATION & SERVICE phases:

-  1  gas type

-  10  domestic hot water mode (parameter not used in this phase)

-  3   insulation  level  of  building  (only  if  external  sensor  is  con

-

nected)

-  45   inclination of thermoregulation curve (OTC), only if  external 

sensor is connected)

-  HH boiler at maximum power

-  LL  boiler at minimum power

-  23  maximum heating adjustment possibility

-  24  minimum heating adjustment possibility.

 

The  parameters  must  be  modified,  by  professionally 

qualified  personnel,  only  if  absolutely  necessary.  The 

manufacturer refuses any responsibility in the case of 

incorrect setting of the parameters.

GAS TYPE (P. 1)

Modify the set value as follows:

-  press  ENTER  to  access  the  parameter  modification  function. 

When ENTER is pressed, the previously set value starts flash

-

ing (fig. 43)

-  turn the domestic hot water temperature selector to change the 

value (1 MTN - 2 LPG)

-  press ENTER to confirm the new value. The digits stop flashing.

MAXIMUM POWER ADJUSTMENT (P. HH)

- Turn the domestic hot water temperature selector till HH is 

shown

-  Use  a  fork  spanner  CH10  to  turn  the  maximum  power  to  the 

value indicated in the multigas table

-  Wait for the pressure on the pressure gauge to stabilise at the 

required value.

Fig. 77

Fig. 78

MINIMUM HEATING ADJUSTMENT POSSIBILITY (P. 24)

Check that the pressure read on the pressure gauge corresponds 

to that shown on the multigas table. 

If it does not, carry out the adjustment operations described below:

-  turn the domestic hot water temperature selector till 24 is shown. 

Wait for the boiler to start

-  press ENTER to access the parameter modification function

-  turn the domestic hot water selector until the pressure gauge 

corresponds to that indicated in the multigas table

-  press ENTER to confirm the new value.

Exit the CALIBRATION & SERVICE function by pressing ESCAPE.

The boiler returns to the “- -” (OFF) status.

To reset, press the   button.

-  Disconnect the pressure gauge and tighten the pressure tap 

screw.

  After adjusting the gas valve, seal it with sealing wax.

After making adjustments:

-  return the temperature set with the ambient thermostat to the 

required position

-  close the panel

-  put back the shell. 

12  - ADJUSTMENTS

Summary of Contents for Exclusive 24 C.A.I.

Page 1: ...and user manual Exclusive 24 C A I 28 C A I EN INSTALLER AND USER MANUAL FR MANUEL D INSTALLATION ET D UTILISATION ES MANUAL DE INSTALACI N Y USO PT MANUAL PARA INSTALA O E USO RO MANUAL DE INSTALARE...

Page 2: ...des con sommations d nergie des produits li s l nergie R glement D l gu UE No 811 2013 R glement D l gu UE N 813 2013 R glement D l gu UE N 814 2013 La caldera EXCLUSIVE es conforme a los requisitos...

Page 3: ...009 142 EEC Directiva eficien Articolul 7 2 i Anexa III din Directiva 92 42 EEC Directiva compatibilitate electromagnetic 2014 30 UE Directiva voltaj redus 2014 35 UE Directiva 2009 125 CE n ceea ce p...

Page 4: ...s Conex o g s Liga o el ctrica Enchimento e esvaziamento Evacua o dos produtos da combust o Dados t cnicos Programa o par metros Regula o e Transfor ma o g s s o aqueles referidos ao instalador os cap...

Page 5: ...Safety measures the boiler should not be used by children or unassisted di sabled people electrical devices or equipment such as switches applian ces etc should not be used if there is a smell of gas...

Page 6: ...is responsible for making sure that the appliance has an adequate earthing system the manu facturer shall not be held liable for eventual damages caused by incorrect usage or failing to earth the boil...

Page 7: ...apacity l h 1 000 1 000 Membrane expansion tank l 8 8 Expansion vessel pre charge CH bar 1 1 DHW operation Maximum pressure bar 6 6 Minimum pressure bar 0 15 0 15 Hot water quantity t 25 C l min 13 7...

Page 8: ...m pressure downstream DHW valve mbar 1 30 3 10 4 00 mm H2 O 13 26 31 61 40 79 9 MULTIGAS TABLE The installation of this product is allowed only in the destination Countries contained in the data plate...

Page 9: ...eclared load profile XL XL Water heating energy efficiency wh 78 78 Daily electricity consumption Qelec 0 124 0 125 kWh Daily fuel consumption Qfuel 25 526 25 647 kWh Annual electricity consumption AE...

Page 10: ...ure reaches 1 to 1 5 bar The boiler produces heating and domestic hot water The control panel fig 13 contains the main boiler control and management functions Fig 13 Fig 14 Domestic hot water temperat...

Page 11: ...er is ready to work about 4 seconds after the cycle ends The display will look like fig 16 If the test is unsuccessful the boiler will not work and a 0 will flash on the display In this case contact t...

Page 12: ...mperature to a safe value 35 C The symbol lights up on the display circulator anti block one operating cycle is performed every 24 hours Switching off for long periods For prolonged absences press the...

Page 13: ...r comfort mode is selected the S A R A Booster fun ction is activated for the heating circuit and reaches the required ambient temperature more quickly DOMESTIC HOT WATER PRE HEATING function If the w...

Page 14: ...g the and symbols fig 39 Contact the Technical Assistance Centre Note Fault in domestic hot water circuit sensor 60 the boiler works regularly but does not ensure the stability of the hot water temper...

Page 15: ...AMETER IS NOT USED ON THIS MODEL DO NOT MODIFY 60 13 THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY 80 14 THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY 5 20 CH MODE 0 OFF 1 ON 2 Mzone...

Page 16: ...sword for accessing the parameter modifications function by turning the domestic hot water temperature selector to the required value The password is located on the back side of the control panel Conf...

Page 17: ...aks in the gas supply circuit Programme the Gas type parameter and adjust the boiler as described in the Adjustments chapter The boiler may only be converted by qualified staff After conversion adjust...

Page 18: ...in charger l installation de la fa on indiqu e au chapitre Fonctions de la chaudi re si la chaudi re n a pas servi pendant longtemps nous con seillons d appeler le Service Apr s vente pour effectuer a...

Page 19: ...rmes en vigueur 5 BRANCHEMENT ELECTRIQUE Pour acc der aux branchements lectriques proc dez de la sorte d visser la vis C de la cache tuyauterie fig 3c sortez le couvercle de son logement en le tirant...

Page 20: ...en tre les l ments doivent tre herm tiques et tous les com posants doivent r sister la temp rature aux condensats et aux sollicitations m caniques Le dispositif contr lant la bonne vacuation de fum es...

Reviews: