13

Exclusive C.A.I.

Troubleshooting

When a fault appears on the display, the flame symbol   goes 

out, a flashing code is shown and the two symbols 

 and 

 appear either together or separately.

For a description of the faults, consult the following table.

(D) Permanent

(T)  Temporary. In this operating status the boiler attempts to eliminate the fault on its own

(

°

)  See NOTE in the next page.

(

*

)  For the “insufficient circuit pressure” fault, proceed with the circuit filling operations described in the 

“Boiler functions” 

chapter.

Symbol

FAULT ID

Alarm 

Symbol 

FLAME FAILURE BLOCK (D) 

10 

YES

NO

LIMIT THERMOSTAT (D) 

20

YES 

NO

FUMES THERMOSTAT (D)

22

YES

YES

INSUFFICIENT SYSTEM PRESSURE (D*)

40

YES

NO

INSUFFICIENT SYSTEM PRESSURE (T*)

41

NO

YES

WATER PRESSURE TRANSDUCER (D) 

42

NO

YES

FALSE FLAME (D)

50

YES

YES

ELECTRONIC BOARD (D) 

51-59

YES

YES

SANITARY PROBE 1 (T°)  

60 

NO 

YES

PRIMARY PROBE (T) 

71 

NO 

YES

LOW TEMPERATURE THERMOSTAT (T) 

77 

NO

YES

Fig. 34

Fig. 35

Info 2

   shows circuit pressure (fig. 31)

Fig. 31

Fig. 32

Fig. 33

S.A.R.A. BOOSTER function 

If the “winter comfort” mode is selected, the S.A.R.A. Booster fun

-

ction is activated for the heating circuit and reaches the required 

ambient temperature more quickly.

DOMESTIC HOT WATER PRE-HEATING function

If the “winter comfort” mode is selected, the domestic hot water 

Preheating function is enabled. This function sets out to keep the 

domestic hot water contained in the boiler hot, thereby considerably 

reducing delivery waiting times.

The 

 function should be selected to reduce power consumption 

in areas where the mains water is not particularly cold.

In this case, the Booster and Preheating functions are not activated.

Info 3

   shows the set heating temperature (fig. 32)

Info 4

  shows the set domestic hot water temperature (fig. 33).

S.A.R.A. function 

If the “winter” mode is selected, the S.A.R.A. 

(Automatic Ambient 

Adjustment System)

 function can be activated.

Turn the heating water temperature selector to a temperature ran-

ging between 55 and 65 °C.

The S.A.R.A. self-adjustment system activates: depending on the 

temperature set on the ambient thermostat and the time taken to 

reach it, the boiler automatically adjusts the heating water tem-

perature to reduce operating times, thereby increasing operating 

comfort and energy saving.

Summary of Contents for Exclusive 24 C.A.I.

Page 1: ...and user manual Exclusive 24 C A I 28 C A I EN INSTALLER AND USER MANUAL FR MANUEL D INSTALLATION ET D UTILISATION ES MANUAL DE INSTALACI N Y USO PT MANUAL PARA INSTALA O E USO RO MANUAL DE INSTALARE...

Page 2: ...des con sommations d nergie des produits li s l nergie R glement D l gu UE No 811 2013 R glement D l gu UE N 813 2013 R glement D l gu UE N 814 2013 La caldera EXCLUSIVE es conforme a los requisitos...

Page 3: ...009 142 EEC Directiva eficien Articolul 7 2 i Anexa III din Directiva 92 42 EEC Directiva compatibilitate electromagnetic 2014 30 UE Directiva voltaj redus 2014 35 UE Directiva 2009 125 CE n ceea ce p...

Page 4: ...s Conex o g s Liga o el ctrica Enchimento e esvaziamento Evacua o dos produtos da combust o Dados t cnicos Programa o par metros Regula o e Transfor ma o g s s o aqueles referidos ao instalador os cap...

Page 5: ...Safety measures the boiler should not be used by children or unassisted di sabled people electrical devices or equipment such as switches applian ces etc should not be used if there is a smell of gas...

Page 6: ...is responsible for making sure that the appliance has an adequate earthing system the manu facturer shall not be held liable for eventual damages caused by incorrect usage or failing to earth the boil...

Page 7: ...apacity l h 1 000 1 000 Membrane expansion tank l 8 8 Expansion vessel pre charge CH bar 1 1 DHW operation Maximum pressure bar 6 6 Minimum pressure bar 0 15 0 15 Hot water quantity t 25 C l min 13 7...

Page 8: ...m pressure downstream DHW valve mbar 1 30 3 10 4 00 mm H2 O 13 26 31 61 40 79 9 MULTIGAS TABLE The installation of this product is allowed only in the destination Countries contained in the data plate...

Page 9: ...eclared load profile XL XL Water heating energy efficiency wh 78 78 Daily electricity consumption Qelec 0 124 0 125 kWh Daily fuel consumption Qfuel 25 526 25 647 kWh Annual electricity consumption AE...

Page 10: ...ure reaches 1 to 1 5 bar The boiler produces heating and domestic hot water The control panel fig 13 contains the main boiler control and management functions Fig 13 Fig 14 Domestic hot water temperat...

Page 11: ...er is ready to work about 4 seconds after the cycle ends The display will look like fig 16 If the test is unsuccessful the boiler will not work and a 0 will flash on the display In this case contact t...

Page 12: ...mperature to a safe value 35 C The symbol lights up on the display circulator anti block one operating cycle is performed every 24 hours Switching off for long periods For prolonged absences press the...

Page 13: ...r comfort mode is selected the S A R A Booster fun ction is activated for the heating circuit and reaches the required ambient temperature more quickly DOMESTIC HOT WATER PRE HEATING function If the w...

Page 14: ...g the and symbols fig 39 Contact the Technical Assistance Centre Note Fault in domestic hot water circuit sensor 60 the boiler works regularly but does not ensure the stability of the hot water temper...

Page 15: ...AMETER IS NOT USED ON THIS MODEL DO NOT MODIFY 60 13 THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY 80 14 THIS PARAMETER IS NOT USED ON THIS MODEL DO NOT MODIFY 5 20 CH MODE 0 OFF 1 ON 2 Mzone...

Page 16: ...sword for accessing the parameter modifications function by turning the domestic hot water temperature selector to the required value The password is located on the back side of the control panel Conf...

Page 17: ...aks in the gas supply circuit Programme the Gas type parameter and adjust the boiler as described in the Adjustments chapter The boiler may only be converted by qualified staff After conversion adjust...

Page 18: ...in charger l installation de la fa on indiqu e au chapitre Fonctions de la chaudi re si la chaudi re n a pas servi pendant longtemps nous con seillons d appeler le Service Apr s vente pour effectuer a...

Page 19: ...rmes en vigueur 5 BRANCHEMENT ELECTRIQUE Pour acc der aux branchements lectriques proc dez de la sorte d visser la vis C de la cache tuyauterie fig 3c sortez le couvercle de son logement en le tirant...

Page 20: ...en tre les l ments doivent tre herm tiques et tous les com posants doivent r sister la temp rature aux condensats et aux sollicitations m caniques Le dispositif contr lant la bonne vacuation de fum es...

Reviews: