3

In some parts of the manual, some symbols are used:

  WARNING = for actions requiring special care and adequate 

preparation

 

FORBIDDEN = for actions THAT MUST NOT be performed

INSTALLER

1  -  GENERAL SAFETY DEVICES

 

Our boilers are built in our plants and checked down to the 

smallest detail in order to protect users and 

fi

 tters from injury. 

After working on the product, quali

fi

 ed personnel must check 

the electrical wiring, in particular the stripped part of conduc-

tors, which must not stick out from the terminal board, avoid-

ing possible contact with live parts of such conductor.

  This instruction manual, together with the user manual, are 

integral parts of the product: make sure that they remain with 

the appliance, even if it is transferred to another owner or 

user, or moved to another heating system. In case of loss 

or damage, please contact your local Technical Assistance 

Service for a new copy.

  Boiler installation and any other assistance and maintenance 

operation must be carried out by quali

fi

 ed personnel accord-

ing to current local and national regulations.

  The installer must instruct the user about the operation of the 

appliance and about essential safety regulations.

  This boiler must only be used for the application it was de-

signed for. The manufacturer declines all contractual and 

non-contractual liability for injury to persons or animals or 

damage to property deriving from errors made during instal-

lation, adjustment and maintenance and from improper use.

  After removing the packaging, make sure the content is in 

good conditions and complete. Otherwise, contact the dealer 

from who you purchased the appliance.

  The safety valve outlet must be connected to a suitable col-

lection and venting system. The manufacturer declines all li-

ability for any damage caused due to any intervention carried 

out in the safety valve.

  Dispose of all the packaging materials in the suitable contain-

ers at the corresponding collection centres.

  Dispose of waste being careful not harm human health and 

without employing procedures or methods which may dam-

age the environment.

  C.A.I. models: the ventilation openings are vital for correct 

combustion.

During installation, inform the user that:

-  in the event of water leaks, the water supply must be shut off and 

the Technical Assistance Service must be contacted immediately

-  the operation pressure of the hydraulic system must be within 1 

and 2 bar, and therefore, must no exceed 3 bar.If necessary, reset 

the pressure as indicated in the paragraph entitled “Filling the 

system”

-  if the boiler has not been used for a long time, it is recommended 

that the Technical Assistance Service performs, at least, the fol-

lowing operations:

•  turn “off” the main switch of the appliance and the general 

switch of the system

•  close the gas and water taps on both the heating and domes-

tic hot water circuits

•  drain the heating and domestic hot water circuits to prevent 

freezing

-  boiler maintenance must be carried out at least once a year. This 

should be booked in advance with the Technical Assistance Ser-

vice.

For safety, always remember that:

  The boiler should not be used by children or unassisted disabled 

people.

  It is dangerous to activate electrical devices or appliances, 

such as switches, home appliances, etc., if you smell gas or 

fumes. In the event of gas leaks, ventilate the room opening 

doors and windows; close the gas general tap; contact the 

quali

fi

 ed personnel from the Technical Assistance Service im-

mediately

  Do not touch the boiler while barefoot or if parts of your body 

are wet or damp

  Before cleaning operations, disconnect the boiler from the 

main power supply by turning “OFF” the two position system 

switch and the main control panel switch

  Do not modify safety and adjustment devices without the 

manufacturer's permission and relative instructions

  Do not pull, disconnect or twist the electric cables coming 

out of the boiler even when it is disconnected from the main 

power supply

  Avoid covering or reducing the size of ventilation openings of 

the installation room

  Do not leave in

fl

 ammable containers and substances in the 

installation room

  Keep packaging materials out of reach of children.

  C.A.I. models: do not cover or reduce the size of the ventila-

tion openings in the room where the boiler is installed. The 

ventilation openings are vital for correct combustion.

2  -  BOILER DESCRIPTION

CIAO C.A.I. e 

is a wall-mounted type B11BS boiler for heating and 

the production of domestic hot water. This type of appliance cannot 

be installed in bedrooms, bathrooms or showers, or in rooms with 

open 

fl

 ues without adequate ventilation.

CIAO C.A.I. e

 boiler is 

fi

 tted with the following safety devices:

-  Safety valve and water pressure switch intervening in cases of 

insuf

fi

 cient or excessive water pressure (max 3 bar-min 0.7 bar).

-  Temperature limit thermostat intervening by putting the boiler into 

safety stop if the temperature in the system exceeds the limit ac-

cording to current local and national regulations

-  Fumes thermostat intervenes by blocking the boiler into a safety 

standstill status if there is a spillage of combustion products in 

the hood; it is located on the right hand tile of the vent-damper 

draught breaker device Intervention of safety devices indicates 

a potentially dangerous boiler malfunction; contact the technical 

assistance service immediately.

The 

fl

 ue gas thermostat not only intervenes for a fault in the com-

bustion products outlet system, but also with various atmospheric 

conditions. One can therefore try to start up the boiler again after 

waiting a short while (see 

fi

 rst ignition section).

  Repeated intervention of the fumes thermostat signi

fi

 es 

evacuation of combustion products into the boiler room with 

possibly incomplete combustion and formation of carbon 

monoxide, 

a highly dangerous condition. Call the techni-

cal assistance service immediately.

  The boiler must never be put into service, not even temporar-

ily, if the safety devices are not working or have been mis-

handled.

  Safety devices must be replaced by the technical assistance 

service, using original manufacturer parts only; see the spare 

parts catalogue supplied with the boiler.

After repairs carry out a trial ignition.

CIAO C.S.I. e

 is a C-type wall-mounted boiler for heating and pro-

duction of domestic hot water: according to the 

fl

 ue gas outlet de-

vice, the boiler is classi

fi

 ed in categories C12, C22, C32, C42, C52, 

C62, C82, C92, C12x, C32x, C42x, C52x, C62x, C82x, C92x.

In con

fi

 guration C, the appliance can be installed in any type of 

EN

Summary of Contents for CIAO e 24 - 28 C.S.I.

Page 1: ...I Installation and User Manual EN Manuel d Utilisation et d Installation Manual de Instalaci n y Uso Manual Usu rio e Instala o Priru nik za Monta u i Kori enje Kurulum ve Kullanim Kilavuzu FR ES PT...

Page 2: ...mandos 75 Elementos funcionales del aparato 77 Circuito hidr ulico 80 Esquemas el ctricos 82 Altura de carga residual del circulador 87 A CIAO e conforme aos requisitos essenciais das seguintes Direc...

Page 3: ...people It is dangerous to activate electrical devices or appliances such as switches home appliances etc if you smell gas or fumes In the event of gas leaks ventilate the room opening doors and windo...

Page 4: ...n the event of leaks due to the overpres sure of the heating system The domestic hot water circuit does not need a safety valve but make sure that the pressure of waterworks does not exceed 6 bar In c...

Page 5: ...er as a lever The table indicates the permitted linear lengths According to the length of the pipes used it is necessary to insert a flange select ing one from those contained in the boiler see the fo...

Page 6: ...esponds to the label data b that piping leaving the boiler is covered by thermal insulation sheath c that flue gas extraction and air suction pipes work correctly d that conditions for regular mainten...

Page 7: ...facturer If it is necessary to adjust it again for example after extraordinary maintenance after replacement of gas valve or after gas conver sion carry out the following procedure The maximum output...

Page 8: ...able in its seat in the air distribution box only C S I model restore connection of the spark plug cable refit the combustion chamber cover and the cover of the air dis tribution box only C S I model...

Page 9: ...saving the boiler can also be connected to a programming clock in order to manage ignition and switching off during the day or week 2A IGNITION First ignition must be carried out by personnel from the...

Page 10: ...Air pressure switch alarm C S I models Fumes thermostat C A I models A03 H2O pressure switch alarm A04 NTC domestic water fault A06 NTC heating fault A07 Parasite flame A11 Electric calibration min an...

Page 11: ...ar C 3 90 3 90 3 90 3 90 Minimum pressure for standard operation bar 0 25 0 45 0 25 0 45 0 25 0 45 0 25 0 45 Selection field of heating water temperature C 40 80 40 80 40 80 40 80 Pump maximum head av...

Page 12: ...ertion of a 45 90 bend m 1 1 5 1 1 5 Hole in wall diameter mm 105 105 Concentric flue gas discharge pipes Diameter mm 80 125 80 125 Maximum length m 12 4 10 Drop due to insertion of a 45 90 bend m 1 3...

Page 13: ...holes mm 1 35 0 76 0 76 Heating maximum gas capacity Sm3 h 3 19 kg h 2 38 2 35 DHW maximum gas capacity Sm3 h 3 19 kg h 2 38 2 35 Heating minimum gas capacity Sm3 h 1 34 kg h 1 00 0 99 DHW minimum gas...

Page 14: ...1 2 48 Heating minimum gas capacity Sm3 h 1 13 kg h 0 84 0 83 DHW minimum gas capacity Sm3 h 1 13 kg h 0 84 0 83 Maximum pressure downstream CH valve mbar 10 40 28 00 36 00 mm W C 106 05 285 52 367 10...

Page 15: ...ne doivent pas utiliser la chaudi re 2 DESCRIPTION DE LA CHAUDI RE CIAO C A I e est une chaudi re de type B11BS murale pour le chauffage et la production d eau chaude domestique Ce type d appareil ne...

Page 16: ...spositif d vacuation correspondant en cas de fuite par surpression de l installation de chauffage Le circuit de l eau sanitaire n a pas besoin de soupape de s curit mais il faut s assurer que la press...

Page 17: ...onduits utilis e il sera n cessaire d ins rer une bride en la choisissant parmi celles contenues dans la chaudi re voir les tableaux report s tout de suite 24 C S I Longueur des conduits 60 100 m Brid...

Page 18: ...ion 3 8 Purge de l eau chaude sanitaire En cas de risque de gel l installation sanitaire doit tre vidang e en proc dant comme suit fermer le robinet g n ral du r seau de distribution d eau ouvrir tous...

Page 19: ...acer le s lecteur de fonction sur OFF et r gler le bouchon de remplissage L fig 13 jusqu ce que la pression atteigne une valeur comprise entre 1 et 1 5 bar Placer ensuite le s lecteur de mode sur la p...

Page 20: ...lles r introduire le br leur dans la chambre de combustion et visser les vis de fixation sur le collecteur du gaz placer la passe c ble avec le c ble bougie dans son logement sur le caisson d air seul...

Page 21: ...on d un thermostat d ambiance contribuera un plus grand confort une utilisation plus rationnelle de la chaleur et une cono mie d nergie en outre la chaudi re peut tre associ e un horloge programmateur...

Page 22: ...rmostat des fum es mod les C A I A03 H2O Alarme de pressostat A04 NTC anomalie eau sanitaire A06 NTC Anomalie de chauffage A07 Flamme parasite A11 Chauffage min et max r glage lectrique ADJ Transitoir...

Page 23: ...90 3 90 3 90 Pression minimum pour fonctionnement standard bar 0 25 0 45 0 25 0 45 0 25 0 45 0 25 0 45 Plage de s lection de la temp rature d eau de chauffage C 40 80 40 80 40 80 40 80 Pompe pr valenc...

Page 24: ...iam tre mm 80 125 80 125 Longueur maximum m 12 4 10 Chute due l insertion d une courbe 45 90 m 1 35 2 2 1 35 2 2 Diam tre du trou de travers e du mur mm 130 130 Conduits d vacuation s par s des fum es...

Page 25: ...m 1 35 0 76 0 76 Capacit maximale de gaz de chauffage Sm3 h 3 19 kg h 2 38 2 35 Capacit maximale de gaz ECS Sm3 h 3 19 kg h 2 38 2 35 Capacit minimale de gaz de chauffage Sm3 h 1 34 kg h 1 00 0 99 Cap...

Page 26: ...t minimale de gaz de chauffage Sm3 h 1 13 kg h 0 84 0 83 Capacit minimale de gaz ECS Sm3 h 1 13 kg h 0 84 0 83 Pression max en aval du robinet en chauffage mbar 10 40 28 00 36 00 mm W C 106 05 285 52...

Page 27: ...ue los ni os o las personas incapacitadas usen la caldera sin asistencia 2 DESCRIPCI N DE LA CALDERA CIAO C A I e es una caldera mural de tipo B11BS para calefacci n y la producci n de agua caliente s...

Page 28: ...para funcionar con el gas disponible esto se comprueba por la leyenda del embalaje y por la etiqueta adhesiva que indica el tipo de gas Es muy importante destacar que en algunos casos las chimeneas ad...

Page 29: ...itud conductos 60 100 m Brida humos F P rdidas de carga de cada curva m 45 90 hasta 0 85 42 1 1 5 de 0 85 a 2 35 44 de 2 35 a 4 25 no instalada 28 C S I Longitud conductos 60 100 m Brida humos F P rdi...

Page 30: ...ncendido de la caldera se deben realizar las siguientes ope raciones conectar la alimentaci n el ctrica de la caldera abrir el grifo de gas presente en la instalaci n para permitir el flujo de combust...

Page 31: ...ci n de la v lvula del gas o bien despu s de una transformaci n de gas seguir los procedimiento que se indican a continuaci n Las regulaciones de la m xima potencia deben ser realizadas en la secuenci...

Page 32: ...de la tarjeta en la tarjeta de control fig 16 si se trata de transformaci n de gas metano en GPL insertar el jumper en la posici n JP3 si se trata de transformaci n de GPL en gas metano quitar el con...

Page 33: ...a caldera adem s puede ser conectada a un cronotermostato para programar encendidos y apagados durante el d a o la semana 2A ENCENDIDO El primer encendido de la caldera debe ser efectuado por personal...

Page 34: ...ci n NTC A07 Llama par sita A11 Regulaci n el ctrica de la calefacci n m nima y m xima ADJ Espera transitoria de encendido 88 C parpadeante Intervenci n de interruptor de presi n de aire Mo delos C S...

Page 35: ...uncionamiento est ndar bar 0 25 0 45 0 25 0 45 0 25 0 45 0 25 0 45 Campo de selecci n de la temperatura del agua caliente C 40 80 40 80 40 80 40 80 Bomba altura de carga m xima disponible para la inst...

Page 36: ...uaci n de humos Di metro mm 80 125 80 125 Longitud m xima m 12 4 10 P rdida por la introducci n de una curva de 45 90 m 1 35 2 2 1 35 2 2 Agujero en la pared di metro mm 130 130 Tubos separados de eva...

Page 37: ...6 0 76 Caudal gas m ximo calefacci n Sm3 h 3 19 kg h 2 38 2 35 Caudal gas m ximo agua sanitaria Sm3 h 3 19 kg h 2 38 2 35 Caudal gas m nimo calefacci n Sm3 h 1 34 kg h 1 00 0 99 Caudal gas m nimo agua...

Page 38: ...imo calefacci n Sm3 h 1 13 kg h 0 84 0 83 Caudal gas m nimo agua sanitaria Sm3 h 1 13 kg h 0 84 0 83 Presi n m x despu s de la v lvula en calefacci n mbar 10 40 28 00 36 00 mm W C 106 05 285 52 367 10...

Page 39: ...apazes n o assistidas 2 DESCRI O DACALDEIRA CIAO C A I e uma caldeira tipo B11BS montada na parede para aquecimento e produ o de gua quente dom stica Este tipo de utens lio n o pode ser instalado em q...

Page 40: ...car se de que a press o do sistema de abastecimento de gua n o supere os 6 bar Em caso de d vida ser oportuno instalar um redutor de press o Antes do acendimento certificar se de que a caldeira esteja...

Page 41: ...abelas indicadas a seguir 24 C S I Comprimento dos tubos 60 100 m Flange de gases da chamin F Perdas de carga de cada curva m 45 90 at 0 85 42 1 1 5 de 0 85 a 2 35 44 de 2 35 a 4 25 n o instalada 28 C...

Page 42: ...causados pela interven o da v lvula de seguran a 4 ACENDIMENTO E FUNCIONAMENTO 4 1 Verifica es preliminares O primeiro acendimento deve ser feito por pessoal competente de um Centro de Assist ncia T c...

Page 43: ...a depois da subs titui o da v lvula do g s ou depois de uma transforma o do g s observar os procedimentos descritos a seguir As regula es da pot ncia m xima devem ser executadas na sequ ncia indicada...

Page 44: ...e compensa o caixa de ar so mente modelos C S I Desconecte o man metro e volte a apertar o parafuso da tomada de press o Para terminar a fun o de calibragem sem a memoriza o dos valores configurados o...

Page 45: ...de um term stato ambiente favorecer um conforto maior uma utiliza o mais racional do calor e uma economia energ tica a caldeira pode al m disso ser combinada a um rel gio programador para gerir acend...

Page 46: ...stato de fumos modelos C A I A03 Alarme de pressostato H2O A04 Avaria de gua quente sanit ria NTC A06 Avaria de aquecimento NTC A07 Chama parasita A11 Calibragem el ctrica aquecimento min e max ADJ Ig...

Page 47: ...s o m nima para funcionamento padr o bar 0 25 0 45 0 25 0 45 0 25 0 45 0 25 0 45 Campo de selec o da temperatura de gua de aquecimento C 40 80 40 80 40 80 40 80 Bomba preval ncia m xima dispon vel par...

Page 48: ...125 80 125 Comprimento m ximo m 12 4 10 Perda para a introdu o de uma curva 45 90 m 1 35 2 2 1 35 2 2 Furo de atravessamento parede di metro mm 130 130 Tubos descarga de fumos separados Di metro mm 80...

Page 49: ...Caudal g s m ximo aquecimento Sm3 h 3 19 kg h 2 38 2 35 Caudal de g s m ximo circuito sanit rio Sm3 h 3 19 kg h 2 38 2 35 Caudal g s m nimo aquecimento Sm3 h 1 34 kg h 1 00 0 99 Caudal de g s m nimo c...

Page 50: ...nimo aquecimento Sm3 h 1 13 kg h 0 84 0 83 Caudal de g s m nimo circuito sanit rio Sm3 h 1 13 kg h 0 84 0 83 Press o m xima jusante da v lvula em aquecimento mbar 10 40 28 00 36 00 mm W C 106 05 285...

Page 51: ...gasa ili dimnih gasova U slu aju propu tanja gasa potrebno je 2 OPIS KOTLA CIAO C A I e je kotao za grejanje i proizvodnju sanitarne vode tipa B11BS koji se instalira na zid Ure aji ovog tipa se ne mo...

Page 52: ...savetuje se da montirate umanjiva pritiska Pre uklju ivanja proverite da li je kotao predvi en za upotrebu sa dostupnim gasom ovo mo ete saznati sa natpisa na ambala i i nalepljenoj etiketi za vrstu...

Page 53: ...0 85 42 1 1 5 od 0 85 do 2 35 44 od 2 35 do 4 25 nije instalirana 28 C S I Du ina cevi 60 100 m Prsten za dimne gasove F Pad pritiska na svakom kolenu m 45 90 do 0 85 43 1 1 5 od 0 85 do 1 7 45 od 1...

Page 54: ...pove ava za 5 C Ova nova po etna vrednost temperature je rezultat ru nog pode avanja temperature grejanja vode i porasta temperature vode od 10 C funkcije S A R A Nakon drugog ciklusa itavog procesa...

Page 55: ...i funkcijama Me utim ako bi bilo neophodno napraviti dodatna uskla ivanja kao to se de ava kada je u pitanju zamena ventila gasa nakon promene gasa tada treba slediti slede a uputstva Pode avanja maks...

Page 56: ...gasa postavite za titnu kutiju sa kablom sve ice na njihovo mesto gde se zadr ava vazduh samo C S I modeli ponovo priklju ite kabl za sve ice ponovo postavite za titni poklopac u komori za sagorevanj...

Page 57: ...te vek proizvodu u slu aju kada je kotao oka en na zid on nije vi e prenosiv i treba tada ostaviti prostor od 5 cm sa strane kako bi se obezbedilo lak e odr avanje instalacija termostata e ose aj komf...

Page 58: ...A01 Alarm elektri nog kvara ACF A01 Alarm grani nog termostata A02 Alarm presostata za vazduh C S I modeli Termostat isparenja C A I modeli A03 Alarm vodenog presostata A04 Kvar NTC sanitarne vode A06...

Page 59: ...isklju enim gorionikom 0 40 0 40 0 10 0 10 Uvo enje grejanja Pritisak Maksimalna temperatura bar 3 90 3 90 3 90 3 90 Minimalni pritisak za pravilan rad bar 0 25 0 45 0 25 0 45 0 25 0 45 0 25 0 45 Pol...

Page 60: ...3 4 Gubitak pri ubacivanju cevi od 45 90 m 1 1 5 1 1 5 Otvor kroz zid pre nik mm 105 105 Koncentri ne cevi za odvod dimnih gasova Pre nik mm 80 125 80 125 Maksimalna du ina m 12 4 10 Gubitak pri ubac...

Page 61: ...0 76 Maksimalni protok gasa za grejanje Sm3 h 3 19 kg h 2 38 2 35 Maksimalni protok gasa za sanitarnu funkciju Sm3 h 3 19 kg h 2 38 2 35 Minimalni protok gasa za grejanje Sm3 h 1 34 kg h 1 00 0 99 Min...

Page 62: ...asa za grejanje Sm3 h 1 13 kg h 0 84 0 83 Minimalni protok gasa za sanitarnu funkciju Sm3 h 1 13 kg h 0 84 0 83 Maksimalni pritisak iza ventila za grejanje mbar 10 40 28 00 36 00 mm W C 106 05 285 52...

Page 63: ...usu al nmas halinde anahtar ev aletleri vb elektrikli cihazlar etkinle tirmek tehlikelidir Gaz ka a olmas halinde kap ve pencereleri a arak oday havaland r n genel gaz muslu unu kapat n derhal Teknik...

Page 64: ...et valf na ihtiya yoktur ancak su tertibat n n 6 bar a mad ndan emin olun phe duyuyorsan z bir bas n azalt c kurun Ate leme ncesinde kombinin mevcut gazla al maya y nelik tasarland ndan emin olun bu a...

Page 65: ...uzunlu u g sterir Kullan lan boru uzunlu una g re kombide yer alanlardan birini a a daki tabloya bak n z se erek bir flan ekl emek gerekir 24 C S I Boru uzunlu u 60 100 m Baca gaz flan F Her dirsek i...

Page 66: ...nu kontrol ediniz 4 2 Cihaz ate leme Kombiyi ba latmak i in a a daki i lemlerin ger ekle tirmesi ge reklidir Kombiye al t r n Yak t ak n sa lamak i in sistemdeki gaz muslu unu a n Mod se iciyi istenil...

Page 67: ...yarlanm t r Ola an st bir bak m gaz valfi de i imi veya gaz d n m nden sonra tekrar ayarlamak gerekirse a a daki prosed r takip edin Maksimum k ayarlamas vas fl personel taraf ndan zel olarak s ral ek...

Page 68: ...ndaki yerine yerle tirin yaln zca C S I Buji kablo ba lant s n yap n Yanma odas kapa n ve hava da t m kutusunun kapa n tak n yaln zca C S I Kontrol panelini kombinin n k sm na do ru evirin Kart kapa n...

Page 69: ...ermostat kurulumu s ve enerji tasarrufuyla birlikte ok daha konforlu ve rasyonel bir kullan m sa layacakt r ayr ca g n ya da hafta boyunca kapatmay ve ate lemeyi y netmek zere kombi bir programlama sa...

Page 70: ...termostat alarm A02 Hava presostat alarm C S I modelleri Duman termostat C A I modelleri A03 H2O presostat alarm A04 NTC ebeke ar zas A06 NTC s tma ar zas A07 Parazit alev A11 Is tma min ve maks elek...

Page 71: ...lemi Bas n maksimum s cakl k bar 3 90 3 90 3 90 3 90 Standart i leyi i in minimum bas n bar 0 25 0 45 0 25 0 45 0 25 0 45 0 25 0 45 Is tma suyu s cakl se im alan C 40 80 40 80 40 80 40 80 Pompa uygun...

Page 72: ...uvardaki delik ap mm 105 105 Konsantrik baca gaz tahliye borular ap mm 80 125 80 125 Maksimum uzunluk m 12 4 10 45 90 dirsek tak lmas nedeniyle d m 1 35 2 2 1 35 2 2 Duvardaki delik ap mm 130 130 Ayr...

Page 73: ...r l r delik ap mm 1 35 0 76 0 76 Maksimum gaz s tma kapasitesi Sm3 h 3 19 kg h 2 38 2 35 DHW maksimum gaz kapasitesi Sm3 h 3 19 kg h 2 38 2 35 Minimum gaz s tma kapasitesi Sm3 h 1 34 kg h 1 00 0 99 DH...

Page 74: ...3 37 kg h 2 51 2 48 Minimum gaz s tma kapasitesi Sm3 h 1 13 kg h 0 84 0 83 DHW minimum gaz kapasitesi Sm3 h 1 13 kg h 0 84 0 83 Maksimum k bas nc CH valf mbar 10 40 28 00 36 00 mm W C 106 05 285 52 36...

Page 75: ...ento em aquecimento Funcionamento em sanit rio Anti congelante indica que est em curso o ciclo anti congelante Temperatura aquecimento sanit rio ou anomalia de funcionamento EN Control panel 1 Digital...

Page 76: ...e u pitanju Funkcija zagrevanja vode ili Sanitarna funkcija vode Antifriz ukazuje da je ciklus antifriz u toku u periodu Temperatura zagrevanja vode sanitarne vode ili postoji odre eni kvar pri funkci...

Page 77: ...77 CIAO e CIAO 24 C S I e CIAO 28 C S I e 10 16 10 16...

Page 78: ...8 Thermostat limite 9 changeur thermique 10 Sonde NTC primaire 11 Ventilateur 12 Tuyau de mesure de d pression 13 Bride de gaz de chemin e 14 Interrupteur de pression de gaz de chemin e 15 Vase d exp...

Page 79: ...na za pra njenje 4 Cirkulaciona pumpa 5 Ventil za odzra ivanje 6 Gorionik 7 Elektroda za paljenje detekciju plamena 8 Grani ni termostat 9 Izmenjiva toplote 10 Primarna NTC sonda 11 Ventilator 12 Mere...

Page 80: ...sanitaria 13 Regulador de presi n de agua 14 By pass 15 Limitador de salida 16 Interruptor de flujo 17 Filtro 18 Grifo de llenado PT CIRCUITO HIDR ULICO 1 Entrada DHW 2 Sa da DHW 3 Entrega de aquecime...

Page 81: ...ing function Qn Nominal capacity Pn Nominal power IP Protection level Pmw Domestic hot water maximum pressure Pms Heating maximum pressure T Temperature Working efficiency D Specific capacity NOx NOx...

Page 82: ...stalar como se indica en el esquema despu s de quitar el puente del conector de 2 v as CN5 Atenci n Entrada TA con baja tensi n de seguridad PT CONEX O DO TERM STATO AMBIENTE T A Term stato ambiente A...

Page 83: ...tection TR1 Transformateur d allumage distant V Ventilateur P F Interrupteur de pression de gaz de chemin e S R Sonde de temp rature de circuit primaire NTC T L Thermostat Limite OPE Op rateur de soup...

Page 84: ...r za izbor zadate vrednosti sanitarne vode P3 Potenciometar za izbor krive regulacije temperature JP1 Premostite da biste osposobili dugmad za kalibraciju JP2 Premostite da biste resetovali tajmer gre...

Page 85: ...de d allumage d tection TR1 Transformateur d allumage distant T F Thermostat de fum es S R Sonde de temp rature de circuit primaire NTC T L Thermostat Limite OPE Op rateur de soupape de gaz P Pompe F...

Page 86: ...date vrednosti sanitarne vode P3 Potenciometar za izbor krive regulacije temperature JP1 Premostite da biste osposobili dugmad za kalibraciju JP2 Premostite da biste resetovali tajmer grejanja i unesi...

Page 87: ...intercambiador de calefacci n en cualquier condici n de la instalaci n First speed primera velocidad Second speed segunda velocidad Third speed tercera velocidad PT Preval ncia residual do circulador...

Page 88: ...88 CIAO e EN A G Water Gas F A G Eau Gaz ES A G Agua Gas PT A G gua G s SRB A G Voda Gas TR A G Su Gaz CIAO 24 C S I e A G CIAO 28 C S I e CIAO 24 28 C A I e fig 1 A G A G...

Page 89: ...AO e C S I SRB mere u mm TR mm olarak l m 50 50 200 50 50 fig 6 fig 9 fig 7 fig 8 EN B Fuse A Supply T A Room thermostat F B Fusible A Alimentation T A Thermostat d ambiance ES B Fusible A Alimentaci...

Page 90: ...90 CIAO e fig 10 fig 10 CIAO 24 C S I e CIAO 28 C S I e fig 11 CIAO 24 C S I e fig 11 CIAO 28 C S I e F F E E F E E X F G F H Y...

Page 91: ...CAPUCH N DE PROTECCI N D CONEXIONES FASTON E TUERCA DE REGULACI N M XIMA POTENCIA F TORNILLO ALLEN PARA LA REGULACI N DEL M NIMO SANITARIO PT A TOMADA DE COMPENSA O MODELO C S I B TOMADA DE PRESS O A...

Page 92: ...i n M X regulaci n m xima calefacci n PT JP1 Ponte habilita o fun o calibragem JP2 Ponte regula o m ximo aquecimento JP3 Ponte selec o MTN GPL PT M N calibragem m nimo aquecimento M X calibragemm ximo...

Page 93: ...93 CIAO e fig 19 CIAO 24 C S I e CIAO 24 28 C A I e CIAO 28 C S I e...

Page 94: ...fig 6a fig 2b fig 3a fig 2a fig 4a fig 5a EN F S S A R A Function F F S Fonction S A R A ES F S Funci n S A R A PT F S Fun o S A R A SRB F S Funkcija S A R A TR F S S A R A Fonksiyonu F S fig 1a fig 7...

Page 95: ......