91
Menu Par.
No.
Display visualis-
ation
Description
Range Factory
setting
UM
Access
type
Cate-
gory
M3 73
Boiler Address
Defines the manner with which the thermal mod-
ule is addressed.
Man-
aging,
Stand-
alone,
Depend-
ent
Stand-
alone
I
Cas-
cade
M3 169
Max. Setp. Offset
Down
Defines the maximum decrease in the primary
circuit's cascade set-point. Is based on the
secondary circuit's probe reading.
0…40
2
°C
I
Cas-
cade
M3 170
Max. Setp. Offset
Up
Defines the maximum increase in the primary
circuit's cascade set-point. Is based on the
secondary circuit's probe reading.
0…40
5
°C
I
Cas-
cade
M3 171
Start Mod. Delay
Fact.
Defines the time in minutes from the moment
the request is triggered until the activation of the
set-point increases or decreases provided for by
Par.169 e 170.
0…60
40
Min.
I
Cas-
cade
M3 176
PID P
Defines the proportional term to change the
set-point of the cascade module based on the
secondary circuit's temperature.
0…1275
25
O
Cas-
cade
M3 177
PID I
Defines the integral term to change the set-point
of the cascade module based on the secondary
circuit's temperature.
0…1275
1000
O
Cas-
cade
M3 178
PID Slew Rate Up
Defines the speed (in °C/100 ms) with which the
set-point of individual modules is increased in
the event the secondary circuit's set-point not
reached (if the value is set to zero, the change is
controlled by the PI of Par. 176 and 177 without
restrictions).
0…25.5
1
O
Cas-
cade
M3 179
PID Slew Rate Dn
Defines the speed (in °C/100 ms) with which the
set-point of individual modules is decreased in
the event the primary circuit's set-point is ex-
ceeded (if the value is set to zero, the change is
controlled by the PI of Par. 176 and 177 without
restrictions).
0…25.5
1
O
Cas-
cade
M4 97
Model
Allow to set the values of Par. from 116 to 128
through some pre-set values which define the
configuration of the inlets and outlets of the
module.
1...2/8...9
I
General
M2 205
Dep. Zone Control
Enables the control of the additional heating
zone managed by the thermal module.
0 = Disabled
1 = Enabled
0…1
0
U
General
M3 158
Next Boiler Start
Delay
This defines the standby time in seconds for the
next boiler in the cascade of cascades to start
up, in normal start mode.
0…1275
1275
Sec.
I
Cas-
cade
M3 159
Next Boiler Off
Delay
This defines the standby time in seconds for the
last boiler which is switched on in the cascade of
cascades to switch off, in normal off mode.
0…1275
1275
Sec.
I
Cas-
cade
M3 160
Delay Quick Start
Next
This defines the standby time in seconds for the
next boiler in the cascade of cascades to start
up, in quick start mode.
0…1275
400
Sec.
I
Cas-
cade
M3 161
Next Quick Stop
Delay
This defines the standby time in seconds for the
last boiler which is switched on in the cascade of
cascades to switch off, in quick off mode.
0…1275
240
Sec.
I
Cas-
cade
M3 167
Number of boilers This defines the number of boilers in a cascade
of cascades.
1…8
1
I
Cas-
cade