52
Menu Par.
No.
Display
visualis-
ation
Description
Range
Default
setting
UM
Access
type
Category
M1
41
DHW
Tank Hold
Warm
Defines the value of a storage cylinder's
delta T required for temperature mainte-
nance. For instance, if set at 3 degrees,
when the storage cylinder is at a set-point
value minus 3 degrees, the thermal mod-
ule is switched on at minimum power to
maintain the temperature to the set-point
plus hysteresis. If this parameter is kept
the same as Par. 36, this function is inac-
tive and the thermal module is switched
on to the maximum power envisaged for
the DHW circuit.
0…10
5
°C
O
DHW
M1
42
DHW
Priority
Defines the priority type:
0 = Time: time priority between the two
circuits defined by Par. 43;
1 = Off: priority for CH;
2 = On: priority for DHW;
3 = Parallel: parallel priority managed on
the basis of the primary circuit's temper-
ature compared to the heating circuit's
set-point.
0…3
2 = On
I
DHW
M1
43
DHW
Max.
Priority
Time
Establishes the time in minutes during
which priority is alternatively allocated to
the DHW and CH circuits when Par. 43 is
set to "time" mode.
1…255
30
Min.
I
DHW
M1
44
DHW
Pump
Overrun
Establishes the overrun time in seconds
for the domestic hot water mode with the
boiler in stand-alone operation; cascaded
operation defines the module's overrun
after switch-off due to thermoregulation.
0…900
60
Sec.
I
DHW
M1
45
DHW
Tank PID
P
Defines the proportional term for modula-
tion during operation of the DHW storage
tank.
0…1255
100
O
DHW
M1
46
DHW
Tank PID I
Defines the integral term for modulation
during operation of the DHW storage
tank.
0…1255
500
O
DHW
M1
47
DHW
Tank PID
D
Defines the derivative term for modulation
during operation of the DHW storage
tank.
0…1255
0
O
DHW
M1
48 DHW tank
set-point
Establishes the DHW storage tank set-
point.
40…71
50
°C
U
DHW
M1
92
Fan
Speed
Maximum
Defines the number of fan rpm at max.
power (it depends on the model and is
defined at Par. 98).
0…12750
Defined by
Par. 98
RPM
I
General
M1
93
Fan
Speed
Minimum
Defines the number of fan rpm at mini-
mum power (it depends on the model and
is defined at Par. 98).
0…12750
Defined by
Par. 98
RPM
I
General
M1
94
Fan
Speed
Ignition
Defines the number of fan rpm when the
boiler is switched on (it depends on the
model and is defined at Par. 98).
0…12750
Defined by
Par. 98
RPM
I
General
M1
116
Prog.
Input 1.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = Water pressure sensor
2 = CH flow switch
3 = Flue pressure switch
0,1,2,3
Defined by
Par. 97
I
General
M1
117 Prog Input
2.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = DHW flow sensor
2 = DHW flow switch
3 = CH flow sensor
0,1,2,3
Defined by
Par. 97
I
General
M1
118 Prog Input
3.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = Drain switch
2 = Gas pressure switch
0,1,2
Defined by
Par. 97
I
General
M1
120 Prog Input
5.
The value of this parameter is defined by
Par. 97.
0 = Disabled
1 = T_Return sensor
2 = Extern switch
0,1,2
Defined by
Par. 97
I
General