SYSTEM MANAGER
104
Status parameters
Register
number
Access
Descrip-
tion
Automatic
conver-
sion
Value
range
L S
100
X
State
See "State"
table
101
X
Status
Same
“State”
value
102
X
Error code
(*)
See "Error"
tables
110
X
Heating
pump
0=off;
1=on
111
X
DHW
pump
0=off;
1=on
112
X
Module
pump
0=off;
1=on
(*) 255= no error
Temperatures/Information
Register
number
Access
Descrip-
tion
Automatic
conver-
sion
Value
range
L S
120
X
Delivery
tempera-
ture
Yes
Depends
on °C/°F
units
121
X
Return
tempera-
ture
Yes
Depends
on °C/°F
units
122
X
DHW tem-
perature
Yes
Depends
on °C/°F
units
123
X
Flue gas
tempera-
ture
Yes
Depends
on °C/°F
units
124
X
System
temper-
atures
(where
available)
Yes
Depends
on °C/°F
units
125
X
Outdoor
tempera-
ture (where
available)
Yes
Depends
on °C/°F
units
140
X
Power
Yes
0..100%
142
X
Ionisation
current
Yes
0..x μA
Dependent information
Register
number
Access Description Automatic
conversion Value range
L S
Dependent 01
300
X
State
See "State"
table
302
X
Error code
See "Error"
tables
303
X
Power
Yes
0..100%
Dependent 02
306
X
State
See "State"
table
308
X
Error code
See "Error"
tables
309
X
Power
Yes
0..100%
Dependent 03
312
X
State
See "State"
table
314
X
Error code
See "Error"
tables
315
X
Power
Yes
0..100%
Dependent 04
318
X
State
See "State"
table
320
X
Error code
See "Error"
tables
321
X
Power
Yes
0..100%
Dependent 05
324
X
State
See "State"
table
326
X
Error code
See "Error"
tables
327
X
Power
Yes
0..100%
Dependent 06
330
X
State
See "State"
table
332
X
Error code
See "Error"
tables
333
X
Power
Yes
0..100%
Dependent 07
336
X
State
See "State"
table
338
X
Error code
See "Error"
tables
339
X
Power
Yes
0..100%
Dependent 08
342
X
State
See "State"
table
344
X
Error code
See "Error"
tables
345
X
Power
Yes
0..100%
Summary of Contents for 20141085
Page 1: ...Installation Manual Modular system Power Max Box Installation Manual EN...
Page 109: ...SYSTEM MANAGER 109...
Page 110: ...SYSTEM MANAGER 110...
Page 111: ...SYSTEM MANAGER 111...