14
Bentone B45-2 RME
For installers
3.5
Nozzle selection
See under Technical data: Recommended nozzle and Nozzle table.
If, after selecting the nozzle, burner type B45-2 has dificulty starting, this
may in some cases be due to the selection of nozzle made for the irst stage.
Selecting a nozzle with a smaller effect in the irst stage may solve the
problem.
3.6
Setting of brake plate and air flow
Prior to commissioning, the basic settings of the burner can be set in
accordance with the diagram. See under Basic settings. Note that it is simply
a matter of a basic setting that should be adjusted retrospectively once the
burner has started. You should then conduct a lue gas analysis and soot
quantity measurement.
3.7
Burner installation
3.7.1
Hole pattern
Make sure the hole pattern on the boiler is designed for burner lange.
Combustion
device
d
1
d
2
d
3
B45-2
Ø 135-(175) 200
M10-M12
Ø (195) 224-260
d
1
d
2
d
3