12
Bentone B45-2 RME
For installers
1
3. INSTALLATION
3.1
Acceptance inspection
Make sure everything is delivered and the goods have not been damaged
during transit. If something is wrong with the delivery, report it to the supplier.
Transport damage must be reported to the shipping company.
3.2
Preparations for installation
Check that the burner's dimensions and capacity range are suitable for the
boiler in question. The power data on the type sign refers to the burner's
min. and max. power.
3.3
Distribution of oil
In order to achieve good reliability, it is important that the oil distribution
system is designed correctly.
Take the following into account:
-
Selection of pipe diameter, pipe length and height difference; see Pump
instruction.
-
Pipelines are to be laid with a minimal number of glands.
-
The pipes are to be laid so that the oil supply hoses are not subjected to
tensile stresses or are excessively bent when the burner is swung out or
removed for service.
-
The oil i lter should be installed so that the i lter cartridge can easily be
replaced or cleaned.
-
Oil-affected parts shall be selected in materials that are capable of
withstanding the medium's physical properties.
-
When installing oil hoses, check that the inlet and return hoses are
i tted to the appropriate connection on the oil pump. The hoses shall be
located so that they do not bend or become subject to tensile load.
-
Bleed the oil system. The oil pump/oil preheater may be damaged if run
dry. The vacuum should not fall below 0 bar in the suction line during
start-up.
3.3.1
Proposed pipe routing for oil distribution
systems without transport pump
1.
Oil i lter
!
Be sure to i ll the burner
oil system before starting
it for the i rst time.
Summary of Contents for B45-2 RME
Page 2: ...2 Bentone B45 2 RME ...
Page 25: ...25 Bentone B45 2 RME For installers ...
Page 30: ...30 Bentone B45 2 RME For installers 7 ELECTRICAL EQUIPMENT 7 1 Wiring diagram LMO24 255 ...
Page 35: ...9 DECLARATION OF CONFIRMITY ...
Page 36: ......
Page 38: ......
Page 39: ...M A C R M M ...
Page 40: ...Enertech AB P O Box 309 SE 341 26 Ljungby www bentone se www bentone com ...