45
Bentone
15.6 Operator level „OPr“
16. Parameter level „PArA“
Two parameter sets, PAr1 und PAr2, can be stored.
Process data
ProC
User data
USEr
(through the setup program only)
Any parameter (up to eight) can be displayed and edited here by using the setup
program.
Program data
Pro
(only with program controller/generator)
A program with up to eight segments is defined here, via the segment setpoints
SPP1
...
SPP8
and segment times
tP 1
...
tP 8
.
Symbol Meaning
SP 1
Setpoint 1 (editable)
SP 2
Setpoint 2 (editable)
SP 3
Setpoint 3 (editable)
SP 4
Setpoint 4 (editable)
SPr
Ramp setpoint (only if configured)
InP1
Measurement of analog input 1
InP2
Measurement of analog input 2 (only if available)
F1
Calculated result of math formula 1 (only if available)
F2
Calculated result of math formula 2 (only if available)
y
Output
trun
Program run time (only with program controller/generator)
trES
Residual program time (only with program controller/generator)
t1
Timer: time 1 (only if configured)
t2
Timer: time 2 (only if configured)
Two parameter sets, PAr1 und PAr2, can be stored.
Parameter
Symbol Value range
Factory setting
Proportional band 1
a
a. with Pb1/2=0, the controller structure is not effective; depending on the display configuration,
these values are shown with the corresponding decimal places
Pb 1
0 ... 9999 °C/°F
0 °C/°F
Proportional band 2
b
b. for controller output 2 (with 3-state controllers)
Pb 2
0 ... 9999 °C/°F
0 °C/°F
Derivative time
c
c. with dt=0, the controller has no differential action (e. g. PI controller)
dt
0 ... 9999 s
80 s
Reset time
d
d. with rt=0, the controller has no integral action (e. g. PD controller)
rt
0 ... 9999 s
350 s
Actuator time tt
tt
5 ... 3000 s
60 s
Cycle time 1
CY 1
0.0 ... 999.9 s
20 s
Cycle time 2
CY 2
0.0 ... 999.9 s
20 s
Contact spacing
db
0.0 ... 999.9 °C/°F 0 °C/°F
Switching differential 1
e
e. for controllers with Pb1/2=0
HYS1
0.0 ... 999.9 °C/°F 1 °C/°F
Switching differential 2
HYS2
0.0 ... 999.9 °C/°F 1 °C/°F
Working point
y0
-100 ... +100 %
0 %
Output limiting (max.)
y1
0 ... 100 %
100 %
Output limiting (min.)
y2
-100 ... +100 %
-100 %