46
Bentone
17. Configuration level „ConF“
Depending on the equipment level of the instrument, individual parameters or groups of
parameters are switched out of display.
Analog selector
With some parameters, you can choose from a series of analog signals. The list below gives
you an overview of the selection options.
0 no function
1 Analog input 1
2 Analog input 2
3 Process value (controller)
4 Setpoint (controller))
5 Ramp end value
6 Program setpoint
13 Controller output level
14 Controller output 1
15 Controller output 2
17.1 Analog inputs “InP”
r
InP1
Analog input 1
r
r
InP2
Analog input 2
r
Parameter
Symbol
Value range
Sensor type
SEnS
0 ...
1
... 11
Linearization
Lin
0 ...
1
... 18
Measurement offset
OFFs
-1999 ...
0
... +9999
Display start
SCL
-1999 ...
0
... +9999
Display end
SCH
-1999 ...
100
... +9999
Factory settings are shown
bold
.
Sensor type
0 no function
6 Heater current 0 — 50 mA AC
1 Resistance thermometer in
3-wire circuit
7 0 — 20 mA
2 Resistance thermometer in
2-wire circuit
8 4 — 20 mA
3 Resistance thermometer in
4-wire circuit
9 0 — 10 V
4 Thermocouple
10 2 — 10 V
5 Resistance transmitter
11 0 — 1 V