9
Bentone
Combustion
device
d
1
d
2
d
3
B 55
ø (155) 165
M14
ø (226) 254-300
B 65
ø (155) 205
M14
ø (226) 254-300
d
1
d
2
d
3
a
b
c
d
e
Burner, type
a
b
c
d
e
B 55-2
2,5-3,0
2,0
6,5-7,0
2,0
6,0-7,0
B 55-3
2,5-3,0
0,0
6,5-7,0
2,0
6,0-7,0
B 65-2
2,5-3,0
2,0
6,5-7,0
2,0
10,0-12,0
B 65-3
2,5-3,0
0,0
6,5-7,0
2,0
10,0-12,0
B 65
e
a
b
c
d
B 55
Nozzle:
45° Solid/semisolid
60° Solid/semisolid
80° Solid/semisolid
Pump pressure
10 bar (8-25 bar)
depending on pump model
Because of the various boiler types with varying furnace geometries and
furnace loads, it is impossible to commit to a certain scattering angle or a
specific distribution pattern.
It should be noted that the scattering angle and distribution pattern changes
with pump pressure.
!
*NB It is important that
the spark does not strike
against the brake plate or
nozzle
2.6 Adjusting the ignition electrodes and brake plate
2.7 Recommended nozzle and pressure
2.8 Burner installation
2.8.1 Hole patten
Make sure the hole pattern on the boiler is designed for burner flange.