31
Bentone
165 101 54
7.2 Components
1.
Pressure gauge port G 1/8”
2.
Nozzle outlet G 1/4”
3.
Suction line G 1/4”
4.
Suction line G 1/4”
5.
Return line G 1/4”
6.
Return line G 1/4”
7.
Return plug
8.
Pressure regulation 4 mm Allen key
7. Instructions Pump RSA 95 & 125
7.1 Technical data
RSA 95
RSA 125
Viscosity range::
1,3-18,0 mm
2
/s
Pressure range at viscosity 1,3-1,8:
5,5-12,0 bar
Pressure range at viscosity 1,8-18,0:
2,5-21,0 bar
Oil temperature:
-10 till+70°C
Nozzle capacity at viscosity 4,3:
150-190 l/h
215-260 l/h
Gear capacity:
225 l/h
294 l/h
Max pressure on the suction and
return side::
4 bar
7.3 Mounting/dismounting by-pass
plug
In a 2-pipe-system excess oil is led back direct to the oil tank. In a 1-pipe-
system the by-pass plug must be removed so that there is a free passage
back to the suction side through the return line with the return port closed.
(Pos.7).
7.4 Purging
On 1-pipe systems it is necessary to purge the pump. On 2-pipe systems
purging is automatic through the return line.
7.5 Replacing the filter
Replace the oil fiter on the oil pump as follows..
• Close the oil valves.
• Unscrew the cover (4 x 5 mm Allen screws).
• Replace the oil filter.
• Replace the cover gasket.
• Refit the cover.
• Open the oil valves.
1
2
3
4
5
6
7
8