3500/93 SYSTEM DISPLAY
42
Class Value
Classification
0
1
2
3
Severe/Fatal Event
Potential Problem Event
Typical logged Event
Reserved
Event Date:
The date the event occurred.
Event Time:
The time the event occurred.
Event Specific:
Provides additional information for the events that use
this field.
Slot:
Indicates the module that the event is associated with.
If a half-height module is installed in the upper slot or
a full-height module is installed, the field will be 0 to
15. If a half-height module is installed in the lower
slot then the field will be 0L to 15L. For example, a
module installed in the lower position of slot 5 would
be 5L.
The event associated with the Display Unit will have
200 added to the slot occupied by Display Interface
Module. Example: Display Interface Module installed
in slot 15. Display Unit will be represented by slot
215.
The following System Event List Messages may be placed in the list by the
Display Interface Module and the Display Unit, and the messages are listed in
numerical order. If you are unable to solve any problems, contact your nearest
Bently Nevada Corporation office.
Flash Memory Failure
Event Number: 11
Event Classification: Potential Problem
Action: Replace the Display Interface Module as soon as possible.
EEPROM Memory Failure
Event Number: 13
Event Classification: Potential Problem
Action: Replace the Display Unit as soon as possible.
Internal Network Failure
Event Number: 30
Event Classification: Severe / Fatal Event
Action: Replace the Display Interface Module immediately.