3500/93 SYSTEM DISPLAY
46
Pass Main Board +12V
(Pass Main Board +12V - Second stage regulator)
Event Number: 157
Event Classification: Severe/Fatal Event
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if the following
component is faulty:
•
the Display Interface Module
Device Configured
Event Number: 300
Event Classification: Typical Logged Event
Action: No action required.
Configuration Failure
Event Number: 301
Event Classification: Severe/Fatal Event
Action: Download a new configuration to the module. If the problem still
exists, replace the module immediately.
Configuration Failure
Event Number: 301
Event Classification: Potential Problem
Action: Download a new configuration to the module. If the problem still
exists, replace the module as soon as possible.
Module Entered Cfg Mode
(Module Entered Configuration Mode)
Event Number: 302
Event Classification: Typical Logged Event
Action: No action required.
Software Switches Reset
Event Number: 305
Event Classification: Potential Problem
Action: Download the software switches to the Display Interface Module. If
the software switches are not correct, replace the Display Interface
Module as soon as possible.
Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: No action required.