When the setpoint Rx is reached the sequence will continue to run but no more chlorine will
be created, chlorine will be created again when the measured Rx value has fallen below the
setpoint Rx.
The unit will measure Ph and Rx (redox) for 40 seconds. This measurement will be stored in
the memory.
If PH is set to -:
If the Ph value is much higher than the setpoint (target value), the Ph dosing pump will run
for 2 min
If the Ph value is lower than the setpoint (target value), the dosing pump does not run.
If the Rx value is lower than the setpoint, chlorine is produced via the electrolysis cell for 4
min
After 6 minutes salt electrolysis and pH dosing will stop, and pH and Redox will be measured
again. The above cycle repeats.
Option 2: Salt time
Here you can set a time in hours and minutes with a
maximum of: 23 hours and 59 minutes.
This means that the unit will only operate on a time
basis to create chlorine, it does not take into account
the measured value of Rx, even if the Rx setpoint is
reached chlorine will continue to be created on a time
basis.
If there is a power failure or flow interruption the timer will reset and go back to full time.
This procedure runs for the set time. After the time has expired the pH dosing and
measuring continues, however, no more chlorine is produced. In the next 24 hours the timer
resumes its settings or set time.
When confirming and after setting the Salt time option, a screen appears with the message:
After each flow or flow interruption, the electrolysis will operate
for xx hours and xx minutes ( your set time values). With
continuous electrical flow, the electrolysis will operate for xx
hours and xx minutes per 24 hours.
Press OK to return.