Alle Rechte und Änderungen vorbehalten.
Subject to change without notice. All rights reserved.
© Bender GmbH & Co KG
UMA710-2-xx-ISO-xx, Manual.docx
Issued: 11.Jan.2016
41
ATICS-Input *)
Digital inputs, galv. isolated
1
Operation mode
adjustable
Function
adjustable
ATICS-Output *)
Contact, galv. isolated
1 volt free changeover contact
Operation mode
adjustable
Function
adjustable
BMS interface
Interface / Protocol
RS-485/BMS
Baud rate
9.6kBit/s
Max. cable length (w/o add. bus amplifier)
≤ 1200 m
Recommended cable: twisted pair, one end of shield connected to PE
min. J-Y(St)Y 2 x 0,8
Termination resistor
120 Ω (0,25 W)
ATICS® BMS-Bus device address
2…90
Connection type power section
Terminals
DIN rail terminals
Cage-clamp spring terminal (at Ie < 65 A, AC3)
1,5 ... 35 mm²
Screw type terminals tightening torque
0,5 ... 0,6 Nm
Cage-clamp spring terminal (at
Ie ≥ 65 A, AC3)
6 ... 35 mm²
Screw type terminals tightening torque
0,5 ... 0,6 Nm
Connection type control section
Terminals
DIN rail terminals
Cage-clamp spring terminal
0,8 ... 2,5 mm²
General Data
EMV immunity
EN 61000-6-2
EMV emission
EN 61000-6-4
Ambient temperature, in use
-25 °C ... +55°C
Climate in use (IEC 60721-3-3)
3K5 (no condensing, no icing)
Climate at transport (IEC 60721-3-2)
2K3 (no condensing, no icing)
Climate for storing (IEC 60721-3-1)
1K4 (no condensing, no icing)
Operation mode
continuous operation
Position
upright
Protection rating components (DIN EN 60529)
IP30
Protection rating terminals (DIN EN 60529)
IP20
Mounting on DIN rail
see tabl
e „Dimensions and weights“
Protection class
SK I (earthed)
Consumption
ATICS-2-63A-xxx-xx: ca.16W
ATICS-2-80A-xxx-xx: ca.28W
Weight approx.
see table „Dimensions and weights“
*)
For further details refer to the technical manual TGH1443 of the ATICS® changeover and monitoring
unit by Bender.