UMA710-2-xx-ISO-xx, Manual.docx
Issued: 11.Jan.2016
28
6.4. Example on how to set the addresses
Please also note the information in the "BMS bus" instruction leaflet.
Two ATICS® units and multiple remote alarm indicators and fault location:
Unit
Parameter
Address setting
ATICS® for area A
Bus- Address
3
first
MK…
(central monitoring)
Address
1
Test- Address
3, 6
Alarm- Address
2*, 3, 4**, 5, 6
second
MK…
for area A
Address
2
Test- Address
3
Alarm- Address
1*, 3, 4**
EDS151 (optional)
Bus- Address
4
ATICS® for area B
Bus- Address
6
first
MK…
for area B
Address
5
Test- Address
6
Alarm-Address
6
* These alarm addresses are required to monitor each other.
** Each EDS channel shall be programmed individually to identify the branch circuit and the room in which
the load is being supplied.